Plan Review Notes
Plan Review Notes For Permit 06010488
Permit Number 06010488
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-11 00:00:00 
 PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
 1) SHT CPROJECT DATA, CODE REFERENCE.
 PLANS REVIEWED AFTER NOV IST 2005
 FBC 2004
 2) SHT D-1 PARTIAL FLOOR PLAN NOTE 19
 RFERENCE TO FLR DRAIN, TO CATCH BASIN.
 NOT APPROVED.
 CONNECT DUMPESTER PAD DRAIN TO EXISTING
 GREASE TRAP.
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISORINDUSTRIAL COORDINATOR,
 LYNN MASSON
  
 OFFICE 561-822-2271
 E-MAIL [email protected]
 FOR CONDITION OF EXISTING GREASE TRAP.
 3) SHT T.1 DEMOLITION PLAN.
 DEMOLITION PERMIT REQUIRED BY LICENSED
 PLUMBING CONTRACTOR, FOR REMOVAL AND
 CAPPING OF ALL PLUMBING FIXTURES.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  