| 2006-02-15 00:00:00 | ******DENIED****** |
| | |
| | PLAN REVIEW ONLY |
| | |
| | 1) IT WOULD APPEAR THAT BASED ON YOUR |
| | OCCUPANT LOAD CALCULATION, THIS BUILDING |
| | WILL NOT MEET THE REQUIREMENT FOR FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEMS. AN |
| | OCCUPANT LOAD SIGN WILL BE REQUIRED AND |
| | MAY BE OBTAINED FROM THE BUREAU OF FIRE |
| | PREVENTION PRIOR TO AN OCCUPATIONAL |
| | LICENSE BEING ISSUED. |
| | |
| | 2) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS. |
| | |
| | 3) PLEASE PROVIDE LIFE SAFETY SHEET TO |
| | ILLUSTRATE REQUIRED MEANS OF EGRESS AND |
| | MAX. TRAVEL DISTANCES. |
| | |
| | 4) PLEASE PROVIDE MORE INFORMATION |
| | REGARDING FLAME RETARDANT/RESISTANCE OF |
| | AWNINGS. |
| | |
| | 5) AN ADDRESS IS REQUIRED ON BUILDING, |
| | AND SHALL BE A MINIMUM OF 6" IN HEIGHT |
| | AND CONTRASTING TO BACKGROUND. |
| | |
| | 6) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILING, |
| | CLASS A,B OR C. |
| | |
| | 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE |
| | REQUIRED AND SHALL BE MOUNTED NOT TO |
| | EXCEED 75' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | 8) LIFE SAFETY TO COMPLY WITH NFPA 101, |
| | 2003 EDITION. |
| | |
| | 9) WILL THE SCOPE OF WORK INCLUDE |
| | HOOD/SUPPRESSION SYSTEMS? SEPARATE SHOP |
| | DRAWINGS/PERMITS REQUIRED. |
| | |
| | 10) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLANS REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |