Plan Review Notes
Plan Review Notes For Permit 06010488
Permit Number 06010488
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-13 00:00:00IN ELEC FOR REVIEW.
 ********** UNSAT ********
  
  
 ** PLEASE KNOW: PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND NOT
 SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE INCLUDE THE
 ARCHITECTUAL'S FIRM LICENSE NUMBER ON
 ALL TITLE BLOCKS FOR ALL SHEETS.
 FAC 61G1-16.004
 THIS IS REQUIRED FOR ALL TRADES AND
 REVIEWS WHETHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S)>
  
 2)NOTE: PLEASE SEE "C" SHEET CONTAINS
 REFERENCE TO THE 2001 FBC. PLEASE KNOW,
 AS OF OCT 1ST, 2005 THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC.
  
 3)NOTE: PLEASE ALSO SEE THAT PLANS SHALL
 REFERENC CURRENT CODES IN EFFECT FOR THE
 NFPA-101 2003, NFPA-72 2002 AND NFPA-70
 2002 EDITIONS.
  
 4)NOTE: PLEASE INDICATE AND SHOW ALL
 CONTINUOUS LOADS AT 125%.
 215.3,230.42
  
 5)NOTE: PLEASE SEE FBC 2004, CHAPTER 13
 FOR ENERGY CODE CORRECTIONS.
 PLEASE SEE 13-101.13, 13-415.1.ABC.1.1,
 ETC
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]