| 2006-02-13 00:00:00 | IN ELEC FOR REVIEW. | | | ********** UNSAT ******** | | | | | | | | | ** PLEASE KNOW: PLANS HAVE ONLY BEEN | | | SUBMITTED FOR "PLAN REVIEW" ONLY AND NOT | | | SUBMITTED FOR PERMIT. | | | | | | | | | 1)NOTE: PLEASE INCLUDE THE | | | ARCHITECTUAL'S FIRM LICENSE NUMBER ON | | | ALL TITLE BLOCKS FOR ALL SHEETS. | | | FAC 61G1-16.004 | | | THIS IS REQUIRED FOR ALL TRADES AND | | | REVIEWS WHETHER OR NOT COMMENT IS MADE | | | BY OTHER REVIEWER(S)> | | | | | | 2)NOTE: PLEASE SEE "C" SHEET CONTAINS | | | REFERENCE TO THE 2001 FBC. PLEASE KNOW, | | | AS OF OCT 1ST, 2005 THE STATE OF FLORIDA | | | ADOPTED THE 2004 FBC. | | | | | | 3)NOTE: PLEASE ALSO SEE THAT PLANS SHALL | | | REFERENC CURRENT CODES IN EFFECT FOR THE | | | NFPA-101 2003, NFPA-72 2002 AND NFPA-70 | | | 2002 EDITIONS. | | | | | | 4)NOTE: PLEASE INDICATE AND SHOW ALL | | | CONTINUOUS LOADS AT 125%. | | | 215.3,230.42 | | | | | | 5)NOTE: PLEASE SEE FBC 2004, CHAPTER 13 | | | FOR ENERGY CODE CORRECTIONS. | | | PLEASE SEE 13-101.13, 13-415.1.ABC.1.1, | | | ETC | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|