| 2006-12-08 19:08:10 | ***UNSAT *** |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE |
| | OF WORK ON THIS PROJECT NEEDS TO BE UPDATED. PLEASE |
| | KNOW EVEN WITH THE PREVIOUS APPLIED VALUE UNDER 433 |
| | AVON WHICH WAS $114K AND THE VALUE ON THIS PERMIT AT |
| | $85K, THE VALUE FOR ALL WORK IN ACTUAL SCOPE IS |
| | EXTREMELY LOW. PLEASE KNOW THE ELECTRICAL ALONE IN THIS |
| | BUILDING IS HIGHER THAN THE APPLIED VALUE FOR THIS |
| | PERMIT. PLEASE KNOW THE VALUE SHALL INCLUDE ALL LABOR |
| | AND MATERIALS. |
| | PLEASE KNOW IF A VALUE IS NOT ADJUSTED FOR ALL WORK AND |
| | MATERIALS AS SHOWN, ONE WILL BE APPLIED BASED ON THE |
| | TABLES FROM THE FBC OR MARSHALL'S AND SWIFT GUIDE. |
| | FBC 108.3 |
| | |
| | 2) NOTE: PLEASE SEE PANEL P5 IS BEING SHOWN AT 600A'S |
| | WITH A 225A FEED. PLEASE VERIFY. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE KNOW AS THE SCOPE INVOLVED EXCEEDS THAT |
| | OF 30%, PLEASE SEE FBC CHAPTER 13 WILL APPLY TO THE |
| | EXISTING OFFICES. THIS WAS GONE OVER IN PREVIOUS |
| | MEETINGS WITH THE ENGINEER AND DESIGN TEAM AND THIS |
| | INFORMATION WAS TO BE UPDATED AND APPLIED TO PLANS. |
| | PLEASE SEE LIGHTING CONTROLS, LIGHTING DENSITIES, ETC. |
| | PLEASE SEE OTHER ROOM(S) ON PLANS WHICH DO NOT SEEM TO |
| | INDICATE A SEPARATE SPACE CONTROL. |
| | PLEASE SEE NEW OUTSIDE LIGHTS REQUIRED TO BE PART OF |
| | THE EXTERIOR LIGHTING POWER ALLOWANCES. |
| | FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | 13-415.2. |
| | |
| | 4) NOTE: PLEASE VERIFY SUB SECTIONS FOR PANELS, 4, AND |
| | 2 NOT ON RISER. |
| | |
| | 5) NOTE: PLEASE PROVIDE A COMPLETE LOAD SUMMARY FOR THE |
| | GENERATOR AS WELL AS THE LOADS ON EACH OF THE EDP AND |
| | THE EDPA. |
| | 220, 702.5 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |