| Notes |
| Date |
Text |
| 2007-01-13 17:30:42 | DENIED | | | REFERENCE: CITY MUNICIPAL CODE | | | UTILITY DEPT STANDARDS | | | | | | 1. SHT P-1.1 900 GAL SAND/OIL INTERCEPTOR DETAIL. | | | UTILITY STANDARDS INDICATE 3" WALLS AND 4" BOTTOM | | | REQUIRED ON ALL INTERCEPTORS. (SEE ATTACHED SHEET). | | | CITY CODE SECTION 90-124(7)(F) STATES "EACH INTERCEPTOR | | | SHALL BE CONSTRUCTED OF STEEL REINFORCED CONCRETE. | | | PLANS CALL FOR "FIBRILLATED POLYPROPLYLENE FIBER". | | | DETAIL ALSO INDICATES 2.5" WALLS AND 3" BOTTOM. THIS | | | DOES NOT MEET MUNICIPAL CODE OR UTILITY STANDARDS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|