| Date |
Text |
| 2006-08-10 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE SEE COMMENTS BELOW, SOME ARE |
| | EXISTING AND SOME ARE NEW BASED ON PLANS |
| | SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE PHASE 1, SHOWS METER |
| | FUTURE AND YET AND METER CAN IS BEING |
| | INSTALLED. PLEASE SEE PHASE II WHICH |
| | SHOWS THE METER BEING INSTALLED AS |
| | EXISTING. |
| | PLEASE KNOW WITHOUT TENANT SEPARATION |
| | THIS METERCAN IS NOT PERMITTED. SEC'S |
| | FROM GUTTER SHALL GO DIRECTLY INTO THE |
| | MAIN2 OF 2. |
| | THIS IS A SINGLE OCCUPANCY , ANY FUTURE |
| | METER CAN WILL BE DONE AT THE TIME OF |
| | SUCH SEPARATION OF TENANTS TAKES PLACE. |
| | THIS WAS THE UDNERSTANDING OF THE LAST |
| | MEETING BY THE DESIGN TEAM. |
| | PLEASE ALSO SEE PHASE ONE FOR RISER |
| | SHOWS CONDUIT AND FEEDERS TO NOTHING |
| | AFTER THE MAIN DISCONNECT. |
| | |
| | 2) NOTE: PLEASE SEE PLANS INDICATE A |
| | PHASE 1 FOR E-1.1, YET TITLE BLOCK CALLS |
| | FOR PHASE II. PLEASE SEE THIS SHEET DOES |
| | NOT CORRELATE WITH PHASING OF THE |
| | PROJECT. |
| | PLEASE SEE SPRAY BOOTH IS BEING SHOWN AS |
| | FUTURE ON PHASE TWO SHEETS, YET SHOWS AS |
| | BEING INSTALLED ON OTHER SHEETS AND ON |
| | PAHSE TWO PANEL SCHEDULES. |
| | PLEASE KNOW ALL INFORMATION AS REQUESTED |
| | FOR LOCATIONS ETC WAS NOT SHOWN FOR |
| | SPRAY BOOTH. |
| | PLEASE SEE NOTE FROM PREVIOUS REVIEW |
| | BELOW; |
| | "PLEASE SEE NEC 511 AND 516. ALL AREAS |
| | AND CLASS LOCATION SHALL BE INDICATED |
| | AND LAYED OUT PER NEC 500, 500.5, 501, |
| | CLASS 1 DIV 1, CLASS 1 DIV 2? |
| | NFPA-88B, 1997 |
| | PLEASE SEE THIS SHOWN WITH A "WAREHOUSE" |
| | OCCUPANCY WHICH DOES NOT SEEM TO |
| | CORRELATE WITH NEW REVISED PLANS AND |
| | PROPOSED WORK. |
| | |
| | 3) NOTE: PLEASE SEE SEAL BY THE ENGINEER |
| | IS NOT CLEAR AND VISABLE WITH ALL |
| | INFORMATION ON SAID SEAL. THIS OFFICE |
| | HAS ATTEMPTED TO SHADE THESE SHEETS TO |
| | SHOW ALL INFORMATION, HOWEVER THIS HAS |
| | NOT BEEN AFFECTIVE. |
| | PLEASE SEE FAC 61G15-23.001 |
| | "RAISED SEAL MUST BE CLEAR AND VISABLE" |
| | |
| | 4) NOTE: MISSING DISCONNECT'S FOR CU'S. |
| | 440.11 |
| | |
| | 5) NOTE: PLEASE SEE MISSING GFI FOR CU'S |
| | 210.63, 210.8. |
| | |
| | 6) NOTE: PLEASE SEE WIRE AND CONDUIT |
| | SCHEDULE AS #2 SHOWS AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" BEFORE THE FIRST |
| | MEANS OF DISCONNECT. PLEASE SEE 250.6, |
| | 250.24 B AS THE "EQUIPMENT GROUNDING |
| | CONDUCTOR" IS ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE SEC'S TO MAIN 1 OF 1. |
| | |
| | |
| | |
| | |
| | |
| | |
| | 6) NOTE: ** IMPORTANT" AS REQUESTED BY |
| | THE BUIDLING REVIEWER ON PREVIOUS NOTES: |
| | ONCE ALL REVIEWS ARE COMPLETE, BEFORE |
| | RESUBMITTING PLANS, PLEASE COMPLETELY |
| | REMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. ONE COPY |
| | OF THE OLD/VOIDED REMOVED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP TO ALLEAVIATE ANY DELAYS |
| | INTHE PROCESS. |
| | |
| | ** PLEASE KNOW, ONE SET OF EACH OF THE |
| | PREVIOUS SUBMITTED ELECTRICAL PLANS |
| | ALONG WITH THE NEW REVISED ELECTRICAL |
| | PLANS ARE BEING RETAINED BY THIS OFFICE |
| | AS EACH SET CONTAINS COMPLETELY |
| | DIFFERENT INFORMATION FOR USE/OCCUPANCY |
| | ETC. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELETRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS, OR COMMENTS |
| | PLEASE CALL. |
| | A CALLED WAS PLACED TO THE ELECTRICAL |
| | ENGINEER'S OFFICE AND A MESSAGE WAS LEFT |
| | AS OF THIS REVIEW TO GO OVER PLANS. |
| | |
| | |