| 2006-07-07 00:00:00 | ********* UNSAT 4TH REVIEW ************ |
| | |
| | PLEASE SEE NOTES BELOW AS MANY ARE NEW |
| | DUE TO COMPLETELY NEW RISERAND MANY |
| | CHANGES ON PLANS. |
| | PLEASE SEE OTHER NOTES PER THIS REVIEW. |
| | * REPRESENTS FBC ADMINISTRATIVE SECTION |
| | 106.1.2 AS ADOPTED BY THE CITY OF WEST |
| | PALM BEACH |
| | |
| | 1) NOTE: IMPORTANT, ONCE ALL REVIEW(S) |
| | ARE DONE AND BEFORE PLANS ARE |
| | RESUBMITTED, PLEASE COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT THE NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE ALSO REMOVE ALL STAPLED PRODUCT |
| | APPROVALS WHICH ARE NOW ATTACHED TO |
| | PLANS. THESE SHOULD BE IN TWO SETS |
| | SEPARATELY FROM PLANS AND NOT ATTACHED. |
| | THIS COMMENT IS FOR OTHER TRADE(S) |
| | SHEETS WHICH WERE LEFT IN SETS. |
| | PLEASE ONLY SUBMIT ONE COPY OF THE |
| | OLD/VOIDED REMOVED SHEETS FOR REFERENCE. |
| | |
| | 2) NOTE: PLEASE BE SURE PLANS REFLECT |
| | THE CURRENT CODES IN EFFECT. PLEASE SEE |
| | ELECTRICAL PLANS REFLECT THE 2001 FBC. |
| | PLEASE ADJUST AND REFERENC THE FOLLOWING |
| | WHICH ARE CURRENTLY UNDER. |
| | 2002 NFPA-70 (DONE), 2002 NFPA-72, 2003 |
| | NFPA-101, 2004 FBC. |
| | |
| | 3) NOTE: PLEASE SEE NOTES BELOW WITH |
| | RESPECT TO SERVICE(S) BEING PROPOSED. |
| | PLEASE KNOW, IN THE MEAN TIME ANY ATS |
| | BEING INSTALLED IN ANY SERVICE REQUIRES |
| | THE MANUFACTURES SPECS/CUT SHEETS TO BE |
| | SUBMITTED. PLEASE BE SURE THESE SHEETS |
| | INDICATE A LISTING BY ANRTL. |
| | 106.1.2 FBC ADMIN SECT, 110.3 |
| | |
| | 4) NOTE: PLEASE CORRELATE PLANS WITH |
| | RISER DIAGRAM. PLEASE SEE SOME SERVICE |
| | EQUIPMENT WHICH IS BEING SHOWN ON RISER, |
| | HOWEVER THESE ARE NOT ON PLANS, POWER OR |
| | LIGHTING SHEETS? (EDP ETC.) |
| | 106.1.2* |
| | |
| | 5) NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | ON PLANS WITH SUBMITTED PANEL SCHEDULES. |
| | PLEASE SEE MANY ITEMS ARE BEING SHOWN |
| | CIRCUITED TO THE PREVIOUS PANEL |
| | SCHEDULES. |
| | PLEASE SEE PANEL SCHEDULES WHICH SHOW |
| | SPARE, YET CIRCUITS ARE ON PLANS. |
| | PLEASE SEE A/C RTU'S BEING SHOWN TO MDP, |
| | HOWEVER MDP DO NOT SHOW THESE ANYMORE. |
| | PLEASE SEE ME LTS ETC. |
| | 106.1.2* |
| | |
| | 6) NOTE: PLEASE KNOW, EM LIGHTING SHALL |
| | BE CIRCUITED PER 700.12E. |
| | PLEASE KNOW, AS THE CIRCUIT FOR THE EM |
| | LTS IS NOW SHOWN AS A BLANK ON PANEL |
| | SCHEDULE. PLEASE KNOW UNLESS THE |
| | GENERATOR WAS PERMITTED UNDER THIS |
| | PERMIT WHICH IT IS NOT, EM LTSWILL BE |
| | REQUIRED WITH BATTERY BACK UP AT A MIN |
| | AT THIS TIME AND UNDER THIS PERMIT. |
| | PLEASE SEE 700.12E, 700.16, LS 101 7.8, |
| | 7.9. |
| | |
| | 7) NOTE: PLEASE SEE"EDP"IS BEING |
| | SHOWN AS 800A MLO AND WITH A LOAD OF |
| | 300+ A'S YET, THE OCP DEVICE SHOWN ON |
| | MDP IS ONLY SHOWN AS 125A'S? PLEASE SEE |
| | THIS EXCEEDS THE RATING OF THE |
| | OVERCURRENT DEVICE. |
| | 240.4,310.16,240, ETC. |
| | |
| | 8) NOTE: PLEASE SEE MDP IS NOTED AND |
| | CIRCUITS ON MDP ETC ARE NOTED WITH A #1 |
| | IN A CIRCLE WHICH MENTIONS TO SEE RISER |
| | FOR FEEDERS, CONDUITS ETC. PLEASE SEE |
| | RISER DOES NOT INDICATE ANY FEEDERS ETC |
| | FROM MDP TO ATS AND FROM ATS TO EDP. |
| | PLEASE REVISE AND ADJUST. |
| | 240.4,310.16, 215.5 ETC |
| | |
| | 9) NOTE: PLEASE KNOW, A DISCONNECTING |
| | MEANS WILL BE REQUIRED GROUPED FOR |
| | FEEDERS COMING FROM FUTURE GENERATOR. |
| | THIS MAY BE SOMETHING PLACED INTO THE |
| | DESIGN AT THIS TIME OR AT A LATER DATE. |
| | PLEASE ALSO SEE NOTES FOR SERVICE. |
| | 225.31-225.39, 110.27 |
| | |
| | 10) NOTE: PLEASE INCLUDE SECT #2 OF P1 |
| | ON RISER DIAGRAM. |
| | PLEASE ALSO INDICATE IF THE PANEL "P1" |
| | CONTAINS OCP FEEDING SECT #2 OR DOES |
| | "P1" CONTAIN "FEED-THRU"LUGS. |
| | PLEASE SHOW. |
| | 106.1.2* |
| | |
| | 11) NOTE: PLEASE SEE ENERGY CALCULATIONS |
| | DO NOT REFLECT LIGHTING INSTALLED AND |
| | LIGHTING ALLOWANCE IN CALCS. IT IS NOTED |
| | ON PLANS AND LETTER FROM ENGINEER THAT |
| | THE "LPD" ARE UNDER MAX LIMITS, YET THE |
| | TOTAL WATTAGE ETC SHOULD BE IN |
| | CALCULATIONS. |
| | FBC 13-415.1.AB.1,13-415.2.ABC.1 |
| | |
| | 12) NOTE: PLEASE CLARIFY NEWOR |
| | EXISTING ROOF TOP GFI(S) FOR A/C |
| | EQUIPMENT. |
| | 210.63,210.8 |
| | |
| | 13) NOTE: PLEASE CLARIFY THE NUMBER OF |
| | AHU'S IN THIS SPACE, AS "M" SHEET |
| | MENITONS AHU'S #1, #2, #3 AND #4?? |
| | ?? |
| | |
| | 14) NOTE: PLEASE SEE NOTICE OF |
| | COMMENCMENT ATTACHED TO PACKAGE HAS |
| | EXPIRED PER FS 713.13(2). |
| | THIS WILL BE REQUIRED OT BE RE-RECORDED |
| | AND SUBMITTED BEFORE PICKING UP PERMIT. |
| | |
| | PLEASE SEE THE FOLLOWING AS COMMENTED |
| | WITH RESPECT TO THE SERVICE. |
| | |
| | ** CALLED ENGINEER ON 7/7/06 AT 4:45 PM |
| | AND LEFT MESSAGE TO CONTACT ME WITH |
| | RESPECT TO THE SERVICE, SEPARATION ETC. |
| | |
| | AS PER CONSULTATION WITH MR. ROBERT AND |
| | OTHERS. THE FOLLOWING TWO OPTIONS MAY BE |
| | DONE. |
| | |
| | 1) IF OPENING BETWEEN THIS SPACE AND THE |
| | ADJOINING FUTURE SPACE IS GOING TO |
| | REMAIN, EVEN WITH THE RATED OVER-HEAD |
| | DOOR, THEN THE ELECTRICAL SERVICE WILL |
| | HAVE TO BE REVISED TO INCLUDE ONLY ONE |
| | SERVICE RISER, ONE METER. |
| | |
| | 2)IF THE WALL IS CLOSED UP TO PROVIDE |
| | THE PROPER TENANT SEPARATION AS REQUIRED |
| | FOR OCCUPANCY TYPES, THEN ONE SERVICE |
| | WITH TWO METERS AND TWO MAINS WOULD BE |
| | PERMITTED. |
| | |
| | PLEASE KNOW ANY EMERGENCY BACK UP SYSTEM |
| | MAY STILL BE INSTALLED AFTER EACH MAIN |
| | ETC. |
| | |
| | ** THIS IS CONSIDERED ONE "BUILDING" |
| | UNDER THE DEFINITIONS OF THE FBC. |
| | ONLY IF SEPARATED BY A "FIRE WALL" WOULD |
| | THESE BE CONSIDERED TWO SEPARATE |
| | BUILDINGS. PLEASE SEE "FIRE WALL" UNDER |
| | DEFINITIONS. |
| | IF CONSTRUCTION OF CLOSING IN THE WALL , |
| | AND CONTRUCTION OF THE EXISTING WALL, |
| | CEILING ETC BETWEEN THE TWO MEET THE |
| | "FIRE WALL" REQUIRMENTS, THEN TWO |
| | SEPARATE SERVICES WILL BE PERMITTED WITH |
| | TWO SEPARATE OPT STAND-BY GENERATOR |
| | SYSTEMS. |
| | |
| | ** PLEASE KNOW, A MEETING SHOULD BE HELD |
| | TO GO COMMENTS, DESIGN ETC BEFORE |
| | RESUBMITTING PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | PLANS WERE ROUTED TO MR ROBERT BROWN |
| | AFTER THE ELECTRICAL REVIEW. |
| 2006-07-02 00:00:00 | SEE DEWEY PALMER WHEN PLANS COME BACK |
| | IN. |