| Plan Review Notes For Permit 06010452 |
| Permit Number |
06010452 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-09-18 00:00:00 | PROVISO: | | | SUBMITTAL FOR THE TEXTILE DUCT & | | | DIFFUSERS ARE NOT LISTED WITH UL. | | | ANOTHER PRODUCT MAY HAVE TO BE SUBMITTED | | | THAT MEET THE CLASS 0 (SURFACE BURNING | | | CHARACTERISTICS OF ZERO) OR CLASS 1 | | | (FLAME SPREAD INDEX <25 AND SMOKE | | | DEVELOPED INDEX <50).THIS ISSUE MUST | | | BE RESOLVED PRIOR TO INSTALLATION OF ANY | | | DUCT. | | | | | | NON-METALIC DUCT SHALL COMPLY WITH | | | 2004 FMC 603.4, DUCTS SHALL BE | | | CONSTRUCTED WITH CLASS 0 OR CLASS 1 DUCT | | | MATERIAL IN ACCORDANCE WITH UL 181. | | | | | | PLEASE NOTE, FABRIC DUCT SUBMITTED | | | (PRIHODA) HAS NO UL LISTING. THE TEST | | | REPORT PAGE 3 UNDER "LIMITATIONS" THERE | | | IS A WARNING WHICH STATES THE FOLLOWING; | | | "THIS DOCUMENT DOES NOT REPRESENT TYPE | | | APPROVAL OR CERTIFICATION OF THE | | | PRODUCT." | | | | | | | | | ADDITIONAL PERMIT REQUIRED FOR THE SPRAY | | | PAINT BOOTH.PLANS AND MANUFACTURER | | | SUBMITTAL DATA ON FILE WITH BUILDING | | | PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. |
|