| 2006-01-20 00:00:00 | ******** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE MISSING FIRM LICENSE |
| | NUMBER ON TITLE BLOCK FOR ARCHITECTUAL |
| | FIRM. FAC 61G1-16.004, FS 481.219 |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE |
| | SIGNED , DATED AND SEALED BY AN |
| | ELECTRICAL ENGINEER, HOWEVER PLANS DO |
| | NOT CONTAIN ANY TITLE BLOCK FOR SAID |
| | ENGINEER OF RECORD AS REQUIRED PER FAC |
| | 61G15-23.002, FS 471.023 |
| | |
| | 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT |
| | SHOWN FOR FUTURE PHONE. IT IS KNOWN TO |
| | THIS OFFICE THE TELEPHONE COMPANY AND |
| | CABLE COMPANY REQUIRES A MIN OF 3/4" |
| | CONDUIT FOR UNDERGROUND INSTALLATIONS. |
| | THIS IS FOR INFORMATIONAL PURPOSE ONLY |
| | AS THIS IS NOT AN NEC REQUIREMENT. |
| | |
| | 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE |
| | IN LOAD CALCS WITH LOAD ON PANEL |
| | SCHEDULE. |
| | PLEASE VERIFY IF INDEED A 40A BRKR WILL |
| | BE USED AS MOST RANGES REQUIRE A MIN OF |
| | 50A. (RANGE RECEPT IS 50A) |
| | PLEASE ALSO VERIFY WIRING METHODS TO BE |
| | USED. PLANS INDICATE CONDUIT AND WIRING, |
| | HOWEVER IF ROMEX IS USED, THE #8 SHOWN |
| | WOULD BE REQUIRED TO BE INCREASED TO #6. |
| | SEE 310.16, 60 DEGREE COL. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS IN THE PANEL |
| | SCHEDULE PROVIDE. IT IS KNOWN THAT NOTE |
| | #7 ON PLANS MENTIONS TO PROVIDE ARC |
| | FAULT BRKRS FOR ALL BEDRMS, HOWEVER |
| | PLEASE SEE 2002 NEC 210.12 WHICH |
| | REQUIRES ALL "OUTLETS" IN BEDRMS TO BE |
| | AFCI PROTECTED. THIS INCLUDES SD'S, |
| | HOWEVER SD'S ARE SHOWN BEING WIRED TO |
| | FAMILY RM RECEPTS. THIS IS OK, HOWEVER |
| | THEN THIS CIRCUIT WOULD ALSO BE REQUIRED |
| | TO BE ARC FAULT, THUS NOTE #7 WOULD NOT |
| | REFERENCE. |
| | |
| | 6)NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES LANSCAPE LTS, HOWEVER PLANS DO |
| | NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN |
| | ON PLANS, THEN LANDSCAPE LIGHTING WILL |
| | BE REQUIRED TO BE UNDER A SEPARATE |
| | PERMIT, WHICH WILL INCLUDE PERMIT, PLANS |
| | AND FEE. |
| | |
| | ** PLEASE VERIFY WIRING METHOD, AS PLANS |
| | INDICATE CONDUIT AND WIRING FOR ALL |
| | CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE |
| | PERMITTED. |
| | THIS IS ONLY A NOTE. |
| | |
| | PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE ON CONTACTING |
| | THIS OFFICE. |
| | |