| Plan Review Notes For Permit 06010445 |
| Permit Number |
06010445 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-19 00:00:00 | DENIED; | | | 1.W/M DRAIN TO BE 3" PER FBC-2004 | | | PLUMBING SEC. 406.3. | | | 2.WATER RISER DIAGRAM; BUILDING SHUTOFF | | | REQUIRED PLEASE SHOW. PLEASE SHOW | | | WATERHAMMER ARRESTORS ON KIT. SINK. | | | 3.REMOVE NOTE 26 FROM PLUMBING | | | SPECIFCATIONS. HOOKING IRRIGATION PUMP | | | TO DOMESTIC WOULD COUSE A CROSS | | | CONNECTION. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|