| 2006-03-01 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | NEED PAID RECEIPT AND STAMPED DRAWINGS. |
| | |
| | 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY |
| | SEC. R401.3 OF 2004 RESIDENTIAL CODE. |
| | |
| | 3- PROVIDE STRUCTURAL BUCK DETAIL USING |
| | 2X BUCK AS REQUIRED BY ENTRY DOORS |
| | PRODUCT APPROVAL SUBMITTED. SEE SEC. |
| | R613.6.2 OF 2004 RESIDENTIAL CODE. |
| | |
| | 4- OWES $374.36 FOR UPDATED BUILDING |
| | VALUATION AND RADON FEES. |
| | |
| | 5- PROVIDE SPECS/SECTION/DETAIL FOR |
| | INSTALLATION OF DECORATIVE STORM |
| | SHUTTERS. SECTION 106.1.2 OF CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 6- DRAWINGS S-2 & S3 ARE MISSING THE |
| | ENGINEER INFO. CHAPTER 471 FL. ST. |
| | |
| | 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR DOOR AND TRANSOM ABOVE |
| | SINGLE ASSEMBLY AS SHOWN ON PLANS FOR |
| | SLIDING GLASS DOORS AT FAMILY RM & |
| | FRENCH DOORS AT MASTER BEDROOM. |
| | OTHERWISE, PROVIDE COMPLETE INFORMATION |
| | FOR STRUCTURAL MULLIONAS REQUIRED BY |
| | SEC. R613.7 OF 2004 RESIDENTIAL CODE. |
| | B) SPECIFY SIZE OF FIXED WINDOW. |
| | |
| | 8- ARCHITECT TO PROVIDE FIRM LICENSE |
| | NUMBER AS REQ'D BY CHAPTER 481 FLORIDA |
| | STATUTES & FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL AS REQ'D BY RULE 9B-72 FOR: |
| | A) FRENCH DOORS W/ TRANSOM ABOVE. |
| | SEE ITEM #7 ABOVE. |
| | B) SLIDING GLASS DOORS WITH TRANSOM |
| | ABOVE. SE ITEM #7 ABOVE. |
| | C) STRUCTURAL MULLIONS. SEE ITEM #7 |
| | D) FIXED WINDOWS. SEE ITEM #7 ABOVE. |
| | E) ALL TRUSS CONNECTORS. SEE PLANS. |
| | F) SINGLE HUNG WINDOWS: FLORIDA |
| | PRODUCT APPROVAL AND DADE COUNTY NOA |
| | SUBMITTED DON'T MATCH. NEED TO PROVIDE |
| | THE EXACT SAME INFORMATION THAT WAS |
| | PROVIDED TO OBTAIN FLORIDA APPROVAL. |
| | INFORMATION SUBMITTED ARE FOR 2 |
| | DIFFERENT MODEL TYPES. FL 3041 ISFOR |
| | MODEL TR-9100. DADE COUNTY NOA SUBMITTED |
| | IS FOR SERIES 2100 WINDOWS. |
| | G) ROOF SHINGLES. NEED TO PROVIDE THE |
| | EXACT SAME DADE COUNTY NOA THAT WAS |
| | SUBMITTED FOR FLORIDA APPROVAL. GO TO |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD |
| | CORRECT NOA. |
| | H) PRECAST LINTELS. |
| | I) ALUMINUM VENTS. |
| | J) ALUMINUM SIDING. |
| | |
| | 10- DESIGNER OF RECORD TO REVIEW AND |
| | APPROVE IN WRITTING ALL PRODUCT |
| | APPROVALS PRIOR TO SUBMITTAL TO THIS |
| | OFFICE AS REQUIRED BY SEC. 106.3.3 OF |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- ARCHITECTURAL DRAWING 1: UPDATE |
| | BUILDING CODE DATA INFORMATION. SEE 2004 |
| | RESIDENTIAL BUILDING CODE. |
| | |
| | 12- DRAWING A-1: A) PROVIDE COMPLETE |
| | DETAILS/SPECS FOR WOOD DECK OUTSIDE |
| | MASTER BEDROOM AND FOR WOOD STEPS AT |
| | REAR COVERED PORCH. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | B) SPECIFY SAFETY GLASS FOR WINDOW IN |
| | BATHROOM LOCATED BETWEEN BEDROOM #1 AND |
| | #2. SEC. R308.4 2004 RESIDENTIAL CODE. |
| | C) UPDATE CODE REFERENCE FOR ATTIC |
| | ACCES. SEE 2004 RESIDENTIAL CODE. |
| | D) UPDATE CODE REFERENCES SPECIFIED |
| | ON GENERAL NOTES AND SCHEDULE NOTES. SEE |
| | 2004 RESIDENTIAL CODE. SEE PLANS. |
| | |
| | 13- DRAWING A-2: A) DESIGN PRESSURES |
| | MARK DOESN'T MATCH MARK SHOWED ON DOORS |
| | AND WINDOWS OPENINGS. REVISE AS REQ'D. |
| | B) SPECIFY SIZE FOR MANUFACTURED |
| | ALUMINUM LOUVER AT FRONT AND BACK |
| | ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 14- DRAWING A-3: A) WHERE IS DETAIL A-5? |
| | SEE COMMENTS IN PLANS ON SECTIONS A & B. |
| | B) SECTION "A": 1)PORCH SECTION CALLS |
| | FOR POURED CONCRETE ARCH. THERE IS NOT |
| | ARCH ON FRONT PORCH. REVISE AS REQUIRED. |
| | 2) WHERE IS DETAIL SHT 5 SPECIFIED |
| | FOR WOOD COLUMN? |
| | 3) SPECIFY FIREBLOCKING MATERIAL AND |
| | LOCATION AT CONCEALED SPACES IN SOFFITS |
| | AND WALLS. SEC. R602.8 2004 RESIDENTIAL |
| | CODE. SEE COMMENTS IN PLANS. |
| | |
| | 15- DRAWING A-4: A) WALL SECTION "A". |
| | UPDATE CODE REFERENCE SPECIFIED FOR |
| | FIREBLOCKING AND SPECIFY FIREBLOCKING |
| | MATERIAL. SEE 2004 RESIDENTIAL CODE. |
| | B) WALL SECTION "B". FOUNDATION |
| | DOESN'T MATCH PLANS. REVISE AS REQUIRED. |
| | C) REVISE PORCH BEAM TO MATCH ELEVATION. |
| | IT IS NOT AN ARCHED BEAM. |
| | |
| | 16- DRAWING S-1: A) ROOF FRAMING PLAN |
| | CALLS FOR CONNECTOR A3 BY REAR PORCH. |
| | THERE IS NOT CONNECTOR A3. SEE TRUSS |
| | ANCHOR SCHEDULE. REVISE AS REQUIRED. |
| | B) WHERE ARE DETAILS A, C AND E KEYED |
| | ON ROOF PLAN?. ALSO, WHERE IS DET SHT |
| | S-2.MAKE SURE ALL KEYED DETAIL AND |
| | PAGE MATCH SPECIFIC DETAIL AND PAGE. SEE |
| | COMMENTS ON PLAN. |
| | |
| | 17- DRAWING S-2: A) TYP. 1 STORY |
| | SECTION: SPECIFY SIZE AND LOCATION OF |
| | ATTIC VENTS. R806 2004 RESIDENTIAL CODE. |
| | B) DETAIL D: 1)HOW IS 2"X6" SILL PLATE |
| | ATTACHED TO CONCRETE BEAM?. |
| | 2) HOW IS 2"X6" "L" BRACE NAILED TO |
| | BOTTOM SILL? |
| | 3) USP RT24 IS A WOOD TO WOOD |
| | CONNECTOR. NEED A WOOD TO MASONRY |
| | CONNECTOR TO ATTACH TO CONCRETE BEAM. |
| | |
| | 18- DRAWING S-3: A) GENERAL NOTES. |
| | UPDATE ALL REFERENCE STANDARDS. SEE 2004 |
| | RESIDENTIAL CODE & 2004 FBC FOR |
| | CORRESPONDING STANDARDS AND SPECIFIC |
| | EDITION. EG: ACI 318-02. SEE PLANS. |
| | B) UPDATE CODE SECTIONS REFERENCED |
| | FOR WIND LOADS, EMERGENCY EGRESS AND |
| | GLASS IMPACT PROTECTION. SEE PLANS. |
| | C) VENTILATION AND EGRESS ARE TWO |
| | DIFFERENT CODE ISSUES. CLEAR OPENING FOR |
| | EGRESS HAS NOTHING TO DO WITH CLEAR |
| | OPENING FOR VENTILATION. REVISE NOTE. |
| | D) TRUSS ANCHOR SCHEDULE: NUMBER OF |
| | NAILS AND UPLIFT LOADS SPECIFIED TO |
| | MATCH THOSE PUBLISHED BY THE |
| | MANUFACTURER IN RECENT CATALOGUE. IF |
| | DIFFERENT NUMBER AND UPLIFT CALCS ARE |
| | SPECIFIED, THEN PROVIDE COMPLETE |
| | ENGINEERING CALCULATIONS TO SHOW WHY |
| | NUMBER AND UPLIFT LOADS ARE CHANGED. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | E) DELETE ADDITION TO STRUCTURE NOTES. |
| | THIS IS NEW CONSTRUCTION AND THEY DON'T |
| | APPLY TO THIS JOB. |
| | |
| | 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL |
| | SIGNATURE, NOT COPY, AS REQUIRED BY |
| | CHAPTER 472 FLORIDA STATUTES. |
| | |
| | 20- STORM SHUTTERS: |
| | A) PROVIDE KEY PLAN. |
| | B) PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE THAT |
| | COVERS ALL REQUIRED INFORMATION TO |
| | PERFORM BUILDING REVIEW AND PRODUCT |
| | COMPLIANCE WITH PROPOSED INSTALLATION. |
| | |
| | 21- ENERGY CALCULATIONS: A) NEED ENERGY |
| | CALCULATIONS USING FORM 600A-2004. |
| | B) CONDITIONED FLOOR AREA DOENS'T |
| | MATCH AREA SHOWN ON PLANS. REVISE. |
| | C) BUILDING ORIENTATION, OVERHANG |
| | LENGTH, OVERHANG HEIGHT AND AREA DON;'T |
| | MATCH PLANS. SEE CHAPTER 13 OF FBC 2004 |
| | FOR PROPER WAY OF CALCULATING THESE |
| | ITEMS. REVISE AS REQUIRED. |
| | D) OWNER TO DATE BOTTOM OF FORM. |
| | |
| | ***NOTE: PLEASE RETURN REVIEWED SET TO |
| | EXPEDITE REVIEW PROCESS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |