| Notes |
| Date |
Text |
| 2006-01-23 00:00:00 | DENIED; | | | 1.KITCHEN SINK NOT VENTED. | | | 2.W/M DRAIN TO BE 3" SEE FBC-2004 | | | PLUMBING SEC. 406.3. | | | 3.WATER HAMMER ARRESTORS ARE REQUIRED ON | | | THE W/M AND KITCHENSINK PER. FBC-2004 | | | RESIDENTIAL SEC. P2903.5 | | | 4.A SHUTOFF VALVE IS REQUIRED ON THE | | | WATER SEVICE PER. RES. CODE SEC | | | P2903.9.1. | | | 5.PLEASE DELETE NOTE 26 TIEING | | | IRRIGATION PUMP TO WATER SYSTEM WOULD BE | | | A CROSS CONNECTION. | | | 6.SEE ELECTRICAL NOT # 1 ABOUT LIC. | | | NUMBER MISSING. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|