| 2006-03-01 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | NEED PAID RECEIPT & STAMPED DRAWINGS. |
| | |
| | 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY |
| | SEC. R401.3 2004 RESIDENTIAL CODE. |
| | |
| | 3- PROVIDE STRUCTURAL BUCK DETAIL USING |
| | 2X BUCK AS REQUIRED BY ENTRY DOORS |
| | PRODUCT APPROVAL SUBMITTED. ALSO, SEE |
| | SEC. R613.6.2 OF 2004 RESIDENTIAL CODE |
| | FOR PROPER BUCK INSTALLATION. |
| | |
| | 4- OWES $296.42 FOR UPDATED BUILDING |
| | VALUATION AND RADON FEES. |
| | |
| | 5- PROVIDE SPECS/SECTION/DETAILS FOR |
| | DECORATIVE STORM SHUTTERS INSTALLATION. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | |
| | 6- DRAWINGS S-1, S-2 AND S-3 ARE MISSING |
| | THE ENGINEER'S INFO. CHAPTER 471 FL. ST. |
| | |
| | 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR FRENCH DOOR WITH TRANSOM |
| | ABOVE SINGLE ASSEMBLY UNIT AS SHOWN ON |
| | PLANS IN REAR ELEVATION. OTHERWISE, |
| | PROVIDE COMPLETE INFORMATION FOR |
| | STRUCTURAL MULLION AS REQ'D BY SEC. |
| | R613.7 2004 RESIDENTIAL CODE. |
| | B) SPECIFY SIZE OF FIXED WINDOW. |
| | |
| | 8- ARCHITECT TO PROVIDE FIRM LICENSE |
| | NUMBER AS REQ'D BY CHAPTER 481 FL. ST. |
| | AND FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL AS REQUIRED BY RULE 9B-72 FOR: |
| | A) FRENCH DOORS WITH W/ TRANSOM |
| | ABOVE. SEE ITEM #7 ABOVE. |
| | B) STRUCTURAL MULLIONS. SEE ITEM #7. |
| | C) FIXED WINDOWS. |
| | D) ALL TRUSS CONNECTORS. SEE PLANS. |
| | E) SINGLE HUNG WINDOWS. PROVIDE SAME |
| | DADE COUNTY NOA THAT WAS SUBMITTED FOR |
| | FLORIDA PRODUCT APPROVAL. |
| | F) ROOF SHINGLES. PROVIDE SAME DADE |
| | COUNTY NOA THAT WAS SUBMITTED FOR |
| | FLORIDA PRODUCT APPROVAL. |
| | G) PRECAST LINTELS. |
| | H) ALUMINUM VENTS. |
| | I) ALUMINUM SIDING. |
| | |
| | 10- DESIGNER OF RECORD TO REVIEW AND |
| | APPROVE IN WRITTING ALL PRODUCT |
| | APPROVALS PRIOR TO SUBMITTAL TO THIS |
| | OFFICE AS REQUIRED BY SEC. 106.3.3 OF |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- ARCHITECTURAL DRAWING A-1: UPDATE |
| | BUILDING CODE DATA INFORMATION. SEE 2004 |
| | RESIDENTIAL CODE. |
| | |
| | 12- DRAWING A-1: A) SPECIFY SAFETY GLASS |
| | FOR BATHROOM WINDOW. SEE PLANS. SEC. |
| | R308.4 2004 RESIDENTIAL CODE. |
| | B) UPDATE CODE REFERENCE FOR ATTIC |
| | ACCES. SEE 2004 RESIDENTIAL CODE. |
| | C) UPDATE CODE REFERENCES SPECIFIED |
| | ON GENERAL NOTES AND SCHEDULE NOTES. SEE |
| | 2004 RESIDENTIAL CODE. |
| | |
| | 13- DRAWING A-2; A) DESIGN PRESSURES |
| | MARK DOESN'T MATCH MARK SHOWED ON DOORS |
| | AND WINDOWS. OPENINGS. REVISE AS REQ'D. |
| | B) SPECIFY SIZE FOR MANUFACTURED |
| | ALUMINUM LOUVER AT FRONT AND BACK. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 14- DRAWING A-3: A) WHERE IS DETAIL A-5? |
| | SEE COMMENTS ON PLANS. |
| | B) SECTION "A": 1) CALLS FOR ALUMINUM |
| | SIDING. FRONT ELEVATION SHOWS STUCCO. |
| | REVISE AS REQUIRED. |
| | 2) WHERE IS DETAIL SH 5 SPECIFIED FOR |
| | WOOD COLUMN SURROUND? |
| | |
| | 15- DRAWING A-4: A) WALL SECTION "A": |
| | UPDATE CODE REFERENCE FOR FIREBLOCKING |
| | AND SPECIFY FIREBLOCKING MATERIAL. SEE |
| | 2004 RESIDENTIAL CODE. |
| | B) WALL SECTION "B": 1) FOUNDATION |
| | DOESN'T MATCH PLANS. REVISE AS REQUIRED. |
| | 2) CLARIFY IF USING ALUMINUM SIDING OR |
| | STUCCO. SEE FRONT ELEVATION. |
| | 3) SPECIFY NAILING SPACING FOR 5/8" |
| | PLYWOOD SHOWN ON PORCH CEILING. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 16- DRAWING S-1: A) FOUNDATION PLAN: |
| | 1) SPECIFY SIZE OF CONTINUOUS FOOTING |
| | AT FRONT PORCH. SEE PLANS. |
| | 2) SPECIFY SIZE OF PRECAST CONCRETE |
| | PAD AT REAR PORCH. SEE PLANS. |
| | 3) WHERE IS DETAIL A ON SHEET S-2? |
| | |
| | B) ROOF FRAMING PLAN: 1) SPECIFY |
| | TRUSS CONNECTORS. |
| | 2) WHERE IS DETAIL 2 SHEET S-2, |
| | DETAIL E SHEET S-2 AND DETAIL C SHEET |
| | S-2?. SEE PLANS. |
| | |
| | 17- DRAWING S-2: A) TYP. 1 STORY |
| | SECTION: SPECIFY SIZE AND LOCATION OF |
| | ATTIC VENTS. R806 2004 RESIDENTIAL CODE |
| | B) DETAIL D: 1) HOW IS 2"X6" SILL |
| | PLATE ATTACHED TO CONCRETE BEAM? |
| | 2) HOW IS 2"X6" "L" BRACE NAILED TO |
| | BOTTOM SILL? |
| | 3) CLARIFY INSTALLATION OF USP TA18. |
| | IT'S SHOWN AS NAILED TO CONCRETE BEAM |
| | INSTEAD OF BEING EMBEDED IN CONCRETE |
| | BEAM. SEE USP CATALOGUE FOR PROPER |
| | INSTALLATION. REVISE AS REQ'D |
| | C) DETAIL A. PORCH FOOTING TO SHOW |
| | CONCRETE STEPS AND DETAILS TO MATCH |
| | SECTION "A" ON DRAWING A-3. |
| | |
| | 18- DRAWING S-3: A) GENERAL NOTES. |
| | UPDATE ALL REFERENCE STANDARDS. SEE 2004 |
| | RESIDENTIAL CODE AND 2004 FBC 2004 FOR |
| | ADOPTED STANDARDS AND SPECIFIC EDITION. |
| | B) UPDATE CODE SECTIONS REFERENCED |
| | FOR WIND LOADS, EMERGENCY EGRESS AND |
| | GLASS IMPACT PROTECTION. SEE PLANS. |
| | C) VENTILATION AND EGRESS ARE 2 |
| | DIFFERENT CODE ISSUES. CLEAR OPENING FOR |
| | EGRESS HAS NOTHING TO DO WITH CLEAR |
| | OPENING FOR VENTILATION. REVISE NOTE. |
| | D) TRUSS ANCHOR SCHEDULE: NUMBER OF |
| | NAILS AND UPLIFT LOADS SPECIFIED TO |
| | MATCH USP CURRENT CATALOGUE. OTHERWISE, |
| | PROVIDE COMPLETE ENGINEERING CALCS FOR |
| | SIZE AND NUMBER OF NAILS THAT ARE |
| | DIFFERENT THAN THOSE PUBLISHED BY THE |
| | MANUFACTURER. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | E) ADDITION TO STRUCTURE NOTES DON'T |
| | APPLY TO THIS JOB. |
| | |
| | 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL |
| | SIGNATURE, NOT COPY, AS REQUIRED BY |
| | CHAPTER 472 FLORIDA STATUTES. |
| | |
| | 20- STORM SHUTTERS: |
| | A) PROVIDE KEY PLAN. |
| | B) PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE THAT |
| | COVERS ALL REQUIRED INFORMATION TO |
| | PERFORM BUILDING REVIEW AND PRODUCT |
| | COMPLIANCE WITH PROPOSED INSTALLATION. |
| | |
| | 21- ENERGY CALCULATIONS: A) NEED ENERGY |
| | CALCULATIONS USING FORM 600A-2004. |
| | B) CONDITIONED FLOOR AREA DOESN'T |
| | MATCH PLANS. |
| | C) BUILDING ORIENTATION, OVERHANG |
| | LENGTH, OVERHANG HEIGHT AND AREA DON'T |
| | MATCH PLANS. REVISE AS REQUIRED. SEE |
| | CHAPTER 13 FBC 2004 FOR PROPER WAY OF |
| | CALCULATING THESE ITEMS. |
| | D) OWNER/AGENT TO SIGN BOTTOM OF FORM |
| | |
| | ***NOTE: TO EXPEDITE REVIEW PROCESS, |
| | PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE TO ORIGINALS. |
| | |
| | JULIO GOMEZ |
| | BUILDIG PLANS EXAMINER |