| 2006-05-16 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06010433 (FOUNDATION NO SLAB) |
| | ADD: 419 LAKEVIEW |
| | CONT: MICHAEL T. LANG |
| | TEL(561)966-5592 |
| | |
| | |
| | -OPERA PLACE- |
| | |
| | ARCHITECT FIRM BERMELLO, AJAMIL & |
| | PARTNERS |
| | HECTOR R. VALVERDE |
| | |
| | ENGINEERS: PEDRO JOSE DUQUESNE |
| | |
| | |
| | 2ND REVIEW |
| | ACTION DENIED |
| | CODE: 2004 FL BUILDING CODE |
| | |
| | * FL BLD CODE = 2004 WEST PALM BEACH |
| | ADMINISTRATIVE CODE |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE NEW |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) COMPLIED. |
| | |
| | 2)FL S S 713.13: |
| | NOTICE OF COMMENCEMENT, TO BE RECORDED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3)COMPLIED. |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 5) THRESHOLD INSPECTION PLAN ONLY 2 SETS |
| | OF REPORT SUBMITTED. THRESHOLD |
| | INSPECTION PLAN SHEETS ARE NOT SIGNED |
| | AND SEALED. |
| | FL S. S. 553.71(7) |
| | (THRESHOLD BUILDING) |
| | ANY BUILDING GREATER THAN (3) STORIES OR |
| | 50 FEET IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN FLORIDA BUILDING CODE WHICH |
| | EXCEEDS 5,000 SQ FT IN AREA AND AN |
| | OCCUPANT LOAD OF GREATER THAN 500 PEOPLE |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER |
| | OF RECORD. THE STRUCTURAL INSPECTION |
| | PLAN MUST BE SUBMITTED TO THE |
| | ENFORCEMENT AGENCY PRIOR TO THE ISSUANCE |
| | OF A PERMIT FOR THE CONSTRUCTION OF |
| | THRESHOLD BUILDING. THE PURPOSE OF THE |
| | STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND |
| | STANDARDS SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH |
| | THE PERMITTED DOCUMENTS. |
| | |
| | 6) TO BE VARIFIED BY H. PISKURA, AT THIS |
| | TIME NO THRESHOLD INSPECTOR SIGNED ON. |
| | WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY, |
| | THIS INFORMATION TO BE ON PLANS. |
| | A) THE EDITION OF THE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. A OR B. |
| | D) COMPLIED. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 11) COMPLIED. |
| | |
| | 12)COMPLIED. |
| | |
| | 13A) SHEET S-3.00 |
| | WIND DESIGN LOADS, FOR PARKING PORTION |
| | OF THE BUILDING AS BEING DESIGNED TO THE |
| | 2001 FBC NOT THE 2004 FBC |
| | |
| | 13B) COMPLIED. ASCE 7-02 |
| | |
| | 14) COMPLIED. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |