| 2006-05-14 00:00:00 | *** UNSAT 2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO CHANGES |
| | MADE ON PLANS. |
| | |
| | PLEASE SEE NOTE BELOW MARKED WITH **, |
| | ARE NOTES TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW. |
| | |
| | ******** UNSAT ************ |
| | |
| | 1)NOTE: OK |
| | |
| | 2)NOTE: OK |
| | |
| | 3)NOTE: OK |
| | |
| | 4)NOTE: OK |
| | |
| | 5)NOTE: OK, SEE NEW NOTES FOR ARC FAULT. |
| | |
| | |
| | NEW NOTE: |
| | |
| | 1) NOTE: PLEASEHOWEVER SEE SD'S ARE |
| | NOW SHOWN WIRED TO LIV RM CIRCUIT, THIS |
| | IS OK, HOWEVER THIS CIRCUIT WOULD NOW |
| | REQUIRED AFCI PROTECTION. SD'S SHOULD BE |
| | ON BEDRM CIRCUIT, BUT NOT REQUIRED TO. |
| | PLEASE EITHER REVISE CIRCUIT NUMBER OR |
| | PROVIDE ARC FAULT ON PANEL SCHEDULE NOW |
| | FOR LIV RM. |
| | |
| | 2)NOTE: OK, HOWEVER PLEASE NOW SEE BATH |
| | CIRCUITS ARE BEING NOTED AS ARC FAULT?? |
| | THIS IS NOT REQUIRED , HOWEVER CAN BE |
| | DONE AS AN ARC FAULT/GFI BRKR IS NOW |
| | MADE. PLEASE CALL TO GO OVER THIS. |
| | |
| | 3) NOTE: PLEASE SEE FRONT AND REAR GFI |
| | RECEPTS WERE REMOVED PER 210.52E ? |
| | |
| | 4) NOTE: PLEASE SEE MISSING KITCHEN |
| | COUNTER SPACE RECEPT GFI PER 210.52C1, |
| | 210.8A6 |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | |
| | |
| | PLEASE SEE REDLINED PLANS FOR MISSING |
| | RECEPTS PER 210.52 |
| | ** PLEASE KNOW, IF PLANS PASS ALL OTHER |
| | REIVEWSA "PROVISO" MAY BE SET UP FOR |
| | THIS PLAN. |
| | IF PLANS ARE DENIED FOR ANY OTHER |
| | COMMENTS, PLEASE REVISE AT THIS TIME. |
| | |
| | PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE ON CONTACTING |
| | THIS OFFICE. |
| | |