| 2006-05-14 00:00:00 | *** UNSAT 2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO CHANGES |
| | MADE ON PLANS. |
| | |
| | PLEASE SEE NOTE BELOW MARKED WITH **, |
| | ARE NOTES TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW. |
| | |
| | ******** UNSAT ************ |
| | |
| | 1)NOTE: NOTE #1 OK |
| | |
| | 2)NOTE:NOTE #2 NO, |
| | |
| | **PLEASE SEEELECTRICAL PLANS ARE |
| | SIGNED , DATED AND SEALED BY AN |
| | ELECTRICAL ENGINEER, HOWEVER PLANS DO |
| | NOT CONTAIN ANY TITLE BLOCK FOR SAID |
| | ENGINEER OF RECORD AS REQUIRED PER FAC |
| | 61G15-23.002, FS 471.023 |
| | SEE E-2 WAS DONE. |
| | |
| | 3)NOTE: OK |
| | |
| | 4)NOTE: OK |
| | |
| | 5)NOTE:OK, HOWEVER SEE SD'S ARE NOW |
| | SHOWN WIRED TO LIV RM CIRCUIT, THIS IS |
| | OK, HOWEVER THIS CIRCUIT WOULD NOW |
| | REQUIRED AFCI PROTECTION. SD'S SHOULD BE |
| | ON BEDRM CIRCUIT, BUT NOT REQUIRED TO. |
| | PLEASE EITHER REVISE CIRCUIT NUMBER OR |
| | PROVIDE ARC FAULT ON PANEL SCHEDULE NOW |
| | FOR LIV RM. |
| | |
| | **PLEASE SEE SD'S ARE SHOWN BEING |
| | WIRED TO MORE THAN ONE CIRCUIT. PLEASE |
| | KNOW, THESE ARE REQUIRED TO BE WIRED |
| | INLINE AND WILL NOT WORK AS SHOWN. |
| | PLEASE BE SURE CIRCUIT SI ONE CONTAINING |
| | ARC FAULT PROTECTION. |
| | |
| | 6)NOTE: OK |
| | |
| | 7)NOTE: OK, HOWEVER PLEASE NOW SEE BATH |
| | CIRCUITS ARE BEING NOTED AS ARC FAULT?? |
| | THIS IS NOT REQUIRED , HOWEVER CAN BE |
| | DONE AS AN ARC FAULT/GFI BRKR IS NOW |
| | MADE. PLEASE CALL TO GO OVER THIS. |
| | |
| | **PLEASE SEE BATH CIRCUIT SHOWN AS |
| | #15 AWG? MISPRINT. |
| | PLEASE ALSO SEE BATH CIRCUITS ARE SHOWN |
| | WITH ARC FAULT BRKRS? |
| | |
| | 8)NOTE: NO, SAME COMMENT. |
| | |
| | ** PLEASE SEE MISSING KITCHEN |
| | COUNTER SPACE RECEPTS PER 210.52C1 |
| | |
| | 9)NOTE:NO, SAME COMMENT |
| | |
| | **PLEASE SEE MISSINGFRONT/REAR GFI |
| | RECEPT PER 210.52E |
| | |
| | 10)NOTE: OK. |
| | |
| | NEW NOTE: |
| | 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS. |
| | |
| | 2) NOTE: PLEASE SEE REDLINED PLANS FOR |
| | MISSING RECEPTS PER 210.52 |
| | |
| | PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE ON CONTACTING |
| | THIS OFFICE. |
| | |