| Plan Review Notes For Permit 06010421 |
| Permit Number |
06010421 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-13 00:00:00 | DENIED; | | | 1. SEE ELECTRICAL PLAN REVIEW NOTE ONE. | | | 2.WATER RISER, WATER HAMMER ARRESTORS | | | ARE REQUIRED ON THE AUTOMATIC CLOTHES | | | WASHER AND ON KITCHEN SINK. FBC-2004 | | | PLUMBING SEC.604.9. | | | 3.HOUSE SHUTOFF VALVE REQUIRED ON WATER | | | SERVICE. SEC.606. | | | 4.3" PIPE REQUIRED FOR AUTOMATIC CLOTHES | | | WASHER. SEC.406.3. | | | 5.KITCHEN SINK WASTE ARM CAN ONLY BE 6' | | | FROM A VENT.SEE TABLE906.1. USE A | | | MACHANICAL VENT UNDER THE SINK. | | | 6. REMOVE NOTE 26. SEE SEC. 608. NO | | | CROSS CONNECTIONS ARE PERMITED IN THE | | | WATER SYSTEM. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|