| 2006-02-09 00:00:00 | *** DENIED *** |
| | 1)ENERGY CALCULATIONS NEED TO BE ON FORM |
| | 600A-04 (2004) PER FBC 13-600.3.A AND |
| | NEED TO BE SIGNED BY OWNER/AGENT. |
| | |
| | 2) ENERGY CAL'S. ARE CALLING FOR 60,000 |
| | TOTAL BTU'S, PLANS ARE CALLING FOR |
| | 90,800 TOTAL BTU'S, PLANS CAN NOT CALL |
| | FOR MORE TGAN THE ENERGY CAL'S. PLEASE |
| | CORRECT. |
| | |
| | 3) NEED TO SHOW SENSIBLE BTU'S. ALSO, ON |
| | PLANS A/C SCHEDULE. |
| | |
| | 4) AHU #1 CONDENSATE DRAIN CAN NOT |
| | DISCHARGE ON THE FRONT PORCH, PER 2004 |
| | FBC/M 1411.3 . |
| | |
| | 5) AHU #1 PROVIED RETURN AIR TO ALL |
| | HABITABLE ROOMS WITH DOORS, SEE NOTE #6. |
| | |
| | 6)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 7) AHU #1 PLEASE SHOW IF YOU ARE USING A |
| | TRUNK LINE OR MIXING BOXES FOR SUPPLY |
| | AIR. |
| | |
| | 8) AHU #2 PROVIED RETURN AIR FOR NEW |
| | OFFICE, KITCHEN, AND FAMILY ROOM, SEE |
| | NOTE #6. |
| | |
| | 9) AHU #2 CAN NOT HAVE AN OPEN RETURN |
| | AIR PLENUM IN THE GARAGE, SEE 2004 FBC/R |
| | 309.1.1 . |
| | |
| | 10) AHU #3 ALL RETURN AIR GRILLS ABOVE |
| | BEDROOM DOORS ARE TO SMALL, SEE NOTE #6. |
| | |
| | 11) PLEASE NOTE WHEN APPLYING FOR YOUR |
| | GENERATOR PERMIT. GENERATOR EXHUST MUST |
| | BE TEN FEET AWAY FROM ANY BUILDING |
| | OPENINGS (WINDOWS, DOORS, ROOF & EAVE |
| | VENTS), AND TEN FEET AWAY FROM ADJECENT |
| | BUILDING OPENS. PER 2004 FBC/M 401.5.1 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |