| 2007-08-09 13:33:23 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER |
| | 1 CITY OF WEST PALM BEACH AMENDMENTS. |
| | |
| | *** REVISION DENIED *** |
| | 1) AS REQUESTED IN LAST REVIEW 6-28-07 NOTE #5 |
| | MECHANICAL PLAN NEEDS TO SHOW THE RETURN AIR GRILLS AND |
| | SIZE FOR 5 TON AHU SEE YELLOW HIGH LIGHT ON PLAN. |
| | |
| | 2) SHOW ON MECHANICAL PLAN HOW THE RETURN AIR FROM THE |
| | NEW WET BAR, NEW PLAY ROOM, AND NEW BEDROOM IS GOING TO |
| | RETURN TO THE AIR HANDLER IF ALL DOORS ARE CLOSED. SEE |
| | 2004 FBC/R M1602.4. |
| | |
| | 3) REVISED MECHANICAL PLANS SUBMITTED SHOWS ONE 5 TON |
| | A/C SYSTEM SERVICING THE WHOLE HOUSE, REVISED ENERGY |
| | CALCULATIONS STATE ONE 5 TON AND ONE 2 TON SERVICING |
| | THE HOUSE, THE TWO MUST COINCIDE. PLEASE CORRECT. |
| | |
| | 4) PREVIOUS MECHANICAL PLANS HAD SHOWN TWO A/C SYSTEMS |
| | TO BE INSTALLED, THIS PLAN ONLY SHOWS ONE SYSTEM, |
| | PLEASE DOUBLE CHECK THE DESIGN BEFORE RE-SUBMITTING. |
| | |
| | 5) BEFORE RE-SUBMITTING PLEASE CHECK THEN RE-CHECK THE |
| | PLANS, ENERGY CALCULATIONS, AND COOLING LOAD |
| | CALCULATIONS TO MAKE CERTAIN THEY ARE ACCURATE, CORRECT |
| | AND COINCIDE WITH EACH OTHER. |
| | |
| | 6)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING |
| | FOUR TIMES THE FEE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |