| 2006-06-17 00:00:00 | |
| | 1) THE CAST-CREET U LINTEL SCHEDULE ON |
| | SHEET A/1 IS MISSING L-17 AND L-27. |
| | ADJUST THE SCHEDULE TO REFLECT THE |
| | DRAWINGS. |
| | |
| | 2) WITH THE ADDITION FO THE REAR PORCH |
| | THE VALUE FOR THIS APPLICATION HAS TO BE |
| | UPDATED . GIVE A FAIR MARKET VALUE FOR |
| | THE ADDITION OF THE PORCH OR WE WILL |
| | ADJUST THE COST USING THE MARSHALL-SWIFT |
| | REFERENCE BOOK. SO, IN ADDITION TO THE |
| | REVISION FEES ADDITIONAL FEES ARE DUE |
| | BASE ON THE SQUARE FOOTAGE OF THE NEW |
| | COVERED POACH |
| | |
| | 3) R802.10.1 TRUSS DESIGN DRAWINGS. |
| | TRUSS DESIGN DRAWINGS, PREPARED IN |
| | CONFORMANCE WITH SECTION R802.10.1 , |
| | SHALL BE PROVIDED TO THE BUILDING |
| | OFFICIAL AND APPROVED PRIOR TO |
| | INSTALLATION. TRUSS DESIGN DRAWINGS |
| | SHALL INCLUDE, AT A MINIMUM, THE |
| | INFORMATION SPECIFIED BELOW. TRUSS |
| | DESIGN DRAWING SHALL BE PROVIDED WITH |
| | THE SHIPMENT OF TRUSSES DELIVERED TO THE |
| | JOBSITE. |
| | |
| | 4) THE DRAWINGS WE HAVE ON FILE STATES |
| | THE TOTAL A/C AREA IS 2306 SQ.FT. |
| | HOWEVER THE NEW DRAWINGS SHOWS THE TOTAL |
| | A/C AREA IS 2414 SQ.FT. SHOW CLEARLY ON |
| | THE NEW DRAWINGS WHERE THE ADDITIONAL |
| | INCREASE IS. |
| | |
| | 5) F.S.472.025 ALL FINAL DRAWINGS, |
| | PLANS, SPECIFICATIONS, PLATS, OR REPORTS |
| | PREPARED OR ISSUED BY THE REGISTRANT IN |
| | ACCORDANCE WITH MINIMUM TECHNICAL |
| | STANDARDS SET BY THE BOARD SHALL BE |
| | SIGNED BY THE REGISTRANT, DATED AND |
| | STAMPED WITH HIS OR HER SEAL. |
| | SEE SHEETS A/5-A/7. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL(561)805-6726 |
| | |
| | |