| Notes |
| Date |
Text |
| 2006-01-31 00:00:00 | *** DENIED *** | | | 1)ENERGY CALCULATIONS NEED TO BE ON FORM | | | 600A-04 (2004) PER FBC 13-600.3.A . | | | | | | 2) NEED MAR MEK INC. OR NELSON MARIN'S | | | LICENSE NUMBER ON MECHANICAL PLANS. | | | | | | 3) NO RETURN AIR IS PROVIDED FOR NEW | | | FAMILY ROOM. | | | | | | 4) NEED TO SHOW SIZE OF THE RETURN AIR | | | GRILL IN THE NEW PARLOR BEHIND DOOR. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|