| Plan Review Notes For Permit 06010368 |
| Permit Number |
06010368 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-30 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE A/C CALCULATIONS ON SHEET A/5 DO | | | NOT MATCH THE MECHANICAL SPEC'S ON SHEET | | | A/7. | | | | | | 2} RECEPTACLE SPACING DOES NOT COMPLY | | | WITH 210.52(A)(1)&(2) IN ANY ROOM OF THE | | | ADDITION. SEE REVIEWED SET OF PLANS FOR | | | EXAMPLES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|