| Plan Review Notes For Permit 06010356 |
| Permit Number |
06010356 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-19 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SHOW THE LOCATIONS OF EXIT | | | LIGHTS AND EMERGENCY LIGHTING. (NEW OR | | | EISTING) | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS | | | REQUIRED AND SHALL MMET THE REQUIREMENT | | | FOR 75' TRAVEL DISTANCE. | | | | | | 3) PLEASE INDICATE IF THESE SPACES ARE | | | PROTECTED BY FIRE SPRINKLER AND OR FIRE | | | ALARM SYSTEMS. IF SO, WILL THIS WORK | | | IMPACT ANY REQUIRED EQUIPMENT? | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|