| Plan Review Notes For Permit 06010356 |
| Permit Number |
06010356 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-13 00:00:00 | DENIED | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) TWO EXISTS ARE REQUIRED FROM | | | MERCANTILE SPACE 129 PER 2004 FBC TABLE | | | 1018.2. BASED ON SCALED DIMENSIONS, AS | | | NONE ARE SPECIFIED ON PLANS. | | | | | | 3) CLARIFY THE DRY STORAGE/ MERCANTILE | | | AREA BETWEEN UNITS 128 AND 129. IS THERE | | | AN OPENING IN THE EXISTING WALL TO THE | | | EXISTING KITCHEN? | | | | | | 4) SHOW THE OPENINGS AT RESTROOMS AND | | | COOLER. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|