| 2006-04-24 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) THE APPLICATION IS TO ADD A DEMISING |
| | WALL/INTERIOR FIREWALL AT UNIT #200 AT |
| | 4047 OKEECHOBEE BLVD. THE NOC GIVES THE |
| | DISCRIPTION OF IMPROVEMENTS AS A TENANT |
| | BUILDOUT OFFICES AT THE SAME LOCATION. |
| | THE PLANS SHOW A NEW TENANT SEPARATION |
| | WALL BETWEEN UNITS 204 AND 205 AND |
| | EXISTING WALLS IN UNITS 205 AND 206. THE |
| | TITLE BOCK ON THE PLANS STATES BUILDOUT |
| | UNIT 205-206 DEMISING WALLS. CLARIFY AND |
| | SPECIFY THE TOTAL SCOPE OF PROPOSED WORK |
| | ON THE PLANS. INDICATE THE TOTAL SCOPE |
| | OF WORK TO BE DONE ON THE APPLICATION |
| | AND NOC, WHICH MUST AGREE WITH THE WORK |
| | INDICATED ON THE PLANS. ADJUST VALUE OF |
| | CONSTRUCTION, IF NECESSARY. INDICATE THE |
| | UNIT NUMBERS WHERE THE WORK WILL BE DONE |
| | ON THE PLANS, APPLICATION AND NOC. |
| | PROVIDE THIS INFORMATION TO THE INTAKE |
| | PERSON WHEN RESUBMITTING SO THAT THE |
| | CORRECT INFORMATION CAN BE INPUT INTO |
| | THE COMPUTER. |
| | |
| | 2) INDICATE THE LOCATION OF FIRE RATED |
| | TENANT SEPARATION WALL THAT YOU ARE |
| | PROPOSING TO INSTALL. PROVIDE THE |
| | INFORMATION REQUESTED IN THE FIRST |
| | REVIEW FOR THE UNITS ON EACH SIDE OF THE |
| | PROPOSED WALL. |
| | |
| | 3) IF YOU ARE ADDING INTERIOR WALLS, THE |
| | EXISTING FIRE SPRINKLER SYSTEM WILL BE |
| | AFFECTED. THE LOCATION OF THE SPRINKLER |
| | HEADS WILL HAVE TO BE ASSESSED TO |
| | DETERMINE IF ADEQUATE COVERAGE WILL BE |
| | PROVIDED. |
| | |