| Plan Review Notes For Permit 06010354 |
| Permit Number |
06010354 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-13 00:00:00 | DENIED | | | | | | 1) SPECIFY THE OCCUPANCY OF AREAS ON | | | EACH SIDE OF THE TENANT SEPARATION | | | WALLS. SEE 2004 FBC 302 | | | | | | 2) SPECIFY THE LOCATIONS OF THE EXITS. | | | SEE FBC 1018. | | | | | | | | | 3) PROVIDE DIMENSIONS ON THE PLANS IN | | | ORDER TO DETERMINE OCCUPANT LOADS. SEE | | | FBC 1004.1.2 | | | | | | 4) CLARIFY THE RESTROOM LAYOUT. | | | LOCATIONS OF WALLS AND DOORS. SEE FBC | | | 1015 AND 1018. | | | | | | 5) CLARIFY WHY A SECTION OF THE ONE HOUR | | | RATED TENANT SEPARATION WALL IS | | | SPECIFIED WITH 2 LAYERS ON 5/8" TYPE X | | | DRYWALL. NOTE: THE UL WALL ASSEMBLY | | | SPECIFIED REQUIRES DRYWALL ON EACH SIDE | | | OF WALL. | | | | | | 6) CLARIFY DEMISING CEILING AS SPECIFIED | | | ON PLANS AT RESTROOMS. IS IT EXISTING, | | | FIRE RATED, ETC.? | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|