2006-02-03 00:00:00BUILDING REVIEW 4TH CHECKLIST:
 1- ENGINEER'S LETTER CALLS FOR 1/2"
 THICK ISO INSULATION. ACCORDING TO THE
 ROOF ASSEMBLY ON PAGE 31 OF DADE COUNTY
 NOA #01-0130.01 THE MINIMUM INSULATION
 THICKNESS IS 1.5". ENGINEER TO REVISE
 LETTER AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.