Plan Review Notes
Plan Review Notes For Permit 06010338
Permit Number 06010338
Review Stop B
Sequence Number 3
Notes
Date Text
2006-02-02 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- SAME COMMENT FROM 2ND CHECKLIST:
 SELECTED FLAT ROOF SYSTEM IS LIMITED TO
 A MAXIMUM DESIGN PRESSURE OF -45PSF AND
 BY GENERAL LIMITATION #9 WHICH DOESN'T
 ALLOW ADDITIONAL NAIL ENHANCING TO
 INCREASE THE DESIGN PRESSURES.
  
 2- A)ENGINEERED CALCULATIONS SUBMITTED
 ARE NOT ALLOWED BECAUSE OF LIMITATION #9
 OF SELECTED ROOF SYSTEM. CALCULATIONS
 CAN ONLY BE PROVIDED WHEN GENERAL
 LIMITATION #7 APPLIES.
  
 B) ADDITIONALY, ENGINEER TO
 CLEARLY IDENTIFY EXACT ROOF ASSEMBLY
 THAT IS REFERENCED IN THE PRODUCT
 APPROVAL WHEN SUBMITTING CALCULATIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712