2006-01-30 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- FLAT ROOF SYSTEM SELECTED DOESN'T
 WORK. SYSTEM IS LIMITED TO A MAXIMUM
 DESIGN PRESSURE OF -45PSF AND BY GENERAL
 LIMITATION #9 WHICH DOESN'T ALLOW
 ADDITIONAL NAIL ENHANCING TO INCREASE
 THE DESIGN PRESSURES AT PERIMETER AND
 CORNER AREAS. ACCORDING TO TABLE 1609.6B
 FBC 2004 NEED ROOF SYSTEM WITH DESIGN
 PRESSURES OF -89PSF OR MORE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER