| 2006-01-30 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: | | | 1- FLAT ROOF SYSTEM SELECTED DOESN'T | | | WORK. SYSTEM IS LIMITED TO A MAXIMUM | | | DESIGN PRESSURE OF -45PSF AND BY GENERAL | | | LIMITATION #9 WHICH DOESN'T ALLOW | | | ADDITIONAL NAIL ENHANCING TO INCREASE | | | THE DESIGN PRESSURES AT PERIMETER AND | | | CORNER AREAS. ACCORDING TO TABLE 1609.6B | | | FBC 2004 NEED ROOF SYSTEM WITH DESIGN | | | PRESSURES OF -89PSF OR MORE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|