| Plan Review Notes For Permit 06010328 |
| Permit Number |
06010328 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-06-07 00:00:00 | *** UNSAT ** 3RD REVIEW ** | | | | | | ** PLEASE SEE NOTES FROMTWO PREVIOUS | | | REVIEWS STILL | | | | | | | | | | | | | | | 2)NOTE:NOTE #2 NO, NOTHING SUBMITTED. | | | PLEASE SEE THE "JOBSITE" ELECTRICAL PLAN | | | WAS VERIFIED, BUT STILLNEED ELECTRICAL | | | FOR VAK PAK PANEL. CIRCUITS, LOADS, | | | CONDUCTOR SIZES (AWG), OCP | | | ETC. ON THE VAK PAK SCHEDULE. | | | NO WIRING DIAGRAM ETC FOR REVIEW. | | | NO GROUNDING DETAIL FOR POOL, LIGHTING, | | | EQUIPMENT PER 680. | | | 215.5 | | | PLEASE SUBMIT ONCE AGAIN. | | | | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SUBMIT ELECTRICAL WIRING | | | DIAGRAM FOR ALL POOL EQUIPMENT AND | | | WIRING. | | | PLEASE PROVIDE GROUNDING DETAIL PER 680. | | | PLEASE SHOW HOW EQUIPMENT IS BEING FED, | | | FROM WHERE, SIZE, OCP, FEEDERS, BRANCH | | | CIRCUITS ETC ETC. | | | | | | 2) NOTE: PLEASE KNOW, IF PLANS COME BACK | | | WITH THE SAME COMMENT NOT ADDRESSED, FS | | | 553.80(2)(B) SHALL APPLY FOR THE PLAN | | | REVIEW PORTION OF THE PERMIT. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|