| Plan Review Notes For Permit 06010328 |
| Permit Number |
06010328 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-09 00:00:00 | *** UNSAT ** 2ND REVIEW ** | | | | | | ** PLEASE SEE NOTE FROM PREVIOUS REVIEW. | | | | | | | | | 1)NOTE: OK, RE-SEALED SHEETS. | | | | | | 2)NOTE:NOTE #2 NO, NOTHING SUBMITTED. | | | PLEASE SEE THE "JOBSITE" ELECTRICAL PLAN | | | WAS VERIFIED, BUT NEED ELECTRICAL FOR | | | VAK PAK PANEL. CIRCUITS, LOADS, AWG, OCP | | | ETC. | | | ** PREVIOUS NOTE ** | | | PLEASE SUBMIT ELECTRICAL WIRING | | | DIAGRAM FOR ALL POOL EQUIPMENT AND | | | WIRING. | | | PLEASE PROVIDE GROUNDING DETAIL PER 680. | | | PLEASE SHOW HOW EQUIPMENT IS BEING FED, | | | FROM WHERE, SIZE, OCP, FEEDERS, BRANCH | | | CIRCUITS ETC ETC. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | ** PLANS ROUTED TO PLUMB AS SHEET DID | | | NOT CONTAIN STAMP FOR REVIEW. |
|