| 2006-02-15 00:00:00 | ********** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.001 WHICH |
| | REQUIRED THE RAISED SEAL TO CHANGE FROM |
| | THE WORDING OF "CERTIFICATE" TO |
| | "LICENSE" BY 2/5/04, HOWEVER AN |
| | EXTENSION WAS GRANTED BY THE FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS TO |
| | DECEMBER 31,2005. |
| | PLEASE KNOW SEAL SHALL CONTAIN THE ABOVE |
| | WORDING ON RAISED SEAL AS REQUIRED. |
| | FS 471.025 |
| | ANY STAMPED PLANS SHALL BECOME "VOID". |
| | ** PLEASE ALSO SEE ONLY THREE SETS ARE |
| | NEED FOR THIS PROJECT , HOWEVER FOUR |
| | SETS WERE SUBMITTED. PLEASE KNOW, IF ALL |
| | FOUR SETS ARE SUBMITTED FOR REVIEW AND |
| | STAMPING, THEN ALL FOUR SETS WILL BE |
| | REQUIRED TO BE SIGNED, DATED AND SEALED |
| | BY ENGINEER. FAC 61G15-23.002 |
| | |
| | 2)NOTE: PLEASE SUBMIT ELECTRICAL WIRING |
| | DIAGRAM FOR ALL POOL EQUIPMENT AND |
| | WIRING. |
| | PLEASE PROVIDE GROUNDING DETAIL PER 680. |
| | PLEASE SHOW HOW EQUIPMENT IS BEING FED, |
| | FROM WHERE, SIZE, OCP, FEEDERS, BRANCH |
| | CIRCUITS ETC ETC. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |