| 2006-04-24 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | MUNICIPAL CODE CITY WPB |
| | |
| | 1. PLEASE SUBMIT A CODE SUMMARY |
| | INDICATING WHICH CODES THE BUILDING HAS |
| | BEEN DESIGNED BY. |
| | 2. PLEASE DECLARE OCCUPANCY FOR THE |
| | BUILDING. SECTION 106.1.1. |
| | 3. PLEASE SUBMIT A SUMMARY CHART |
| | SUPPLYING INFORMATION ON THE AMOUNT OF |
| | UNITS, UNIT TYPES WITH AMOUNT OF EACH, |
| | AND SHOW COMPLIANCE WITH SECTIONS |
| | 11-9.1.2, 11-9.1.3, 11-9.1.4 & 11-9.2.3. |
| | INDICATE THE ROOM NUMBER FOR EACH |
| | REQUIREMENT, IE: ACCESSIBLE ROOM, ROOMS |
| | WITH ROLL IN SHOWERS, ACCOMODATIONS FOR |
| | PERSONS WITH HEARING IMPAIRMENTS ETC. |
| | THIS WILL BE REQUIRED FOR THE PERCENTAGE |
| | FOR ALL UNITS. (HOTEL) |
| | 4. PLEASE INDICATE HOW ALL THE UNITS |
| | FROM THE PREVIOUS COMMENT WILL BE MADE |
| | AVAILABLE, AND IF THESE UNITS WILL BE |
| | SOLD AS CONDO'S WILL THEY BE MADE |
| | AVAILABLE AT ALL TIMES. SECTION 106.1.1. |
| | 5. PLEASE INDICATE UNIT LOCATIONS AND |
| | ROOM NUMBERS CONSIDERED "CONDO |
| | OCCUPANCY". FAIR HOUSING WILL BE |
| | REQUIRED FOR THOSE UNITS. IF ALL UNITS, |
| | ALL UNITS SHALL BE REQUIRED TO MEET |
| | FHA-91 DESIGN MANUAL REQUIREMENTS ONE |
| | THRU SEVEN. |
| | 6. SHTS A2.91 7 A2.10.1 INDICATE THE |
| | LOCATION OF ALL PRIMARY AND SECONDARY |
| | DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. |
| | 7. SHT A2.11.1 SHOW THE LOCATION OF |
| | SECONDARY ROOF DRAINS FOR THE AREA SOUTH |
| | OF THE ELEVATOR EQUIPMENT ROOM, RO2. |
| | SECTION 1107. |
| | 8. SHTS A6.1.1 THRU A6.14.2 ALL WATER |
| | CLOSETS SHALL BE 1'6" OFF THE WALL TO |
| | THE CENTER LINE OF THE FIXTURE. THIS IS |
| | AN ABSOLUTE MENSUREMENT PER PAGE 6.5 FHA |
| | DESIGN MANUAL, AND FIGURE 28 SECTION |
| | 11.3.1 FBC-2004. MEASUREMENTS SHOWN ARE |
| | 1'63/8" OR 1'6" MIN. PLEASE CORRECT THE |
| | W/C MEASUREMENTS. |
| | 9. SHTS A6.1.1 THRU A6.14.2 INDICATE THE |
| | CORRECT HEIGHT OF THE LAV AS 34" AS |
| | REQUIRED ON PAGE 7.52 FHA DESIGN MANUAL. |
| | 10. SHTS A6.1.1 THRU A6.14.2 ALL |
| | ACCESSIBLE UNITS SHOW THE FOLLOWING: |
| | FOR W/C'S: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | B. 11-4.16.6 DISPENSERS |
| | FOR LAVS: |
| | A. 1-4.19.4 EXPOSED PIPES & SURFACES |
| | FOR TUBS: |
| | A. 11-4.20.5 CONTROLS |
| | B. 11-4.20.6 SHOWER UNIT |
| | FOR SHOWERS: |
| | A. 11-4.21.3 SEAT |
| | B. 11-4.21.4 GRAB BARS |
| | C. 11-4.21.5 CONTROLS |
| | D. 11-4.21.6 SHOWER UNIT |
| | E. 11-4.21.7 CURBS |
| | 11. SUBMIT A LEGEND SHOWING THE AMOUNT |
| | OF UNITS, AND INDICATE UNIT TYPES. |
| | INDICATE THE AMOUNT OF ACCESSIBLE UNITS, |
| | AMOUNT OF UNITS WITH ROLL-IN SHOWER, |
| | AMOUNT OF UNITS WITH ACCOMMODATIONS FOR |
| | PERSONS WITH HEARING IMPAIRMENTS, AND |
| | UNITS FOR HOTEL, MOTEL AND CONDOMINIUM |
| | SPECIAL ACCESSIBILITY FEATURE. SECTIONS |
| | 11-9.1.2, 11-9.1.3, 11-9.1.4 AND |
| | 11-9.2.3. INDICATE THE UNIT NUMBERS FOR |
| | EACH REQUIREMENT. |
| | 12. SHTS A6.1.1 THRU A6.14.2 ALL |
| | ACCESSIBLE UNITS, PER SECTION 11-9.2(7) |
| | KITCHENETTS INDICATE PARALLEL APPROACH. |
| | THIS IS NOT APPROVED PER SECTION |
| | 11-4.24.5. FORWARD APPROACH IS REQUIRED, |
| | AND CABINET DOORS ARE NOT APPROVED IN |
| | THE CLEAR FLOOR SPACE. PLEASE SUBMIT AN |
| | ELEVATION SHOWING COMPLIANCE WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | 13. SHTS A6.1.1 THRU A6.14.2 ALL FHA |
| | UNITS WITH A 2ND BATHROOM, SHOW THE |
| | OPENING DIMENSION FOR THE WATER CLOSET. |
| | MINIMUM 33" REQUIRED. W/C SHALL BE 18" |
| | OFF THE WALL TO CENTER OF FIXTURE, (IF |
| | WALL ADJACENT TO FIXTURE), OR MINIMUM OF |
| | 18" OFF ONE FIXTURE AND MINIMUM OF 15" |
| | OFF THE OTHER FIXTURE. SEE PAGES 6.7, |
| | 7.43, 7.44, 7.45, & 7.46. |
| | 14. SHT A8.1.1 FINISH SCHEDULE FOR THE |
| | COMMON AREA IS NOT COMPLETE. SECTION |
| | 106.1.1. |
| | 15. SHT A8.2.1 REINFORCING AT THE TUB, |
| | SHOW REINFORCING AT THE HEAD OF THE TUB |
| | PER PAGE 6.9 FHA DESIGN MANUAL. |
| | 16. SHT P0.1 CODE IS FBC-2004. CHANGE |
| | CODE REFERENCES. |
| | 17. SHT P2.0 GAS PIPING FROM THE METER |
| | TO THE GAS RISERS. ONLY ONE RISER SHOWN. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | 18. SHTS P2.0 & P2.1 GREASE LINE INTO |
| | THE BUILDING SHOWS NO RISER FROM BELOW |
| | GRADE. SHT A2.1.1 DOES NOT SHOW A |
| | KITCHEN ON THE FIRST FLOOR. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | 19. SHT P2.1 GAS LINES SHOWN UNDER THE |
| | SLAB OF THE BUILDING. PLEASE INDICATE |
| | HOW THE PIPING WILL BE PRESSURE TESTED |
| | AND INSPECTED, THEN AFTER THE PIPING |
| | TEST AND INSPECTION, SHALL HAVE CONDUIT |
| | INSTALLED OVER THE PIPE AS REQUIRED IN |
| | SECTIONS 404.11 AND 406.4. SHOW THE |
| | CONDUIT DETAIL SHOWING COMPLIANCE WITH |
| | SECTION 404.11. |
| | 20. SHT P2.1 5" COMBINATION WASTE/VENT |
| | STACK, (#33) SHOWS 4" ON THE HORIZONTAL |
| | OFFSET. PLEASE CLARIFY. SECTION 704.2 |
| | THE SIZE OF THE DRAINAGE PIPING SHALL |
| | NOT BE REDUCED IN THE DIRECTION OF FLOW. |
| | 21. SHT P2.2 GAS RISER DIAGRAM INDICATES |
| | THE GAS FOR THE KITCHEN FLOOR RISES UP |
| | ABOVE THE SECOND FLOOR. ONLY ON RISER |
| | SHOWN. PLEASE CORRELATE RISER AND FLOOR |
| | PLAN. SECTION 106.1.1. |
| | 22. SHT P2.2 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTION 1106 & 1107 AND ALL SUBSECTIONS. |
| | SHOW SQUARE FOOTAGE AREA AND SHOW 1/2 |
| | AREA OF ALL VERTICAL WALLS ADDED TO |
| | CALCULATIONS. IF SECONDARY ROOF DRAINS |
| | WILL BE SCUPPERS, THEY WILL BE SIZED PER |
| | SECTIONS 1101.7, 1107.3 AND TABLE |
| | 1106.7. THE SIZING OF SCUPPERS CAN NOT |
| | BE DETERMINED WITH REFERENCE TO THE |
| | DEFLECTION OF THE ROOF. PLEASE NOTE IN |
| | CALCULATIONS. |
| | 23. SHT P2.3 DOMESTIC WATER PUMP ROOM |
| | INDICATES A FLOOR DRAIN. NO PIPING IS |
| | SHOWN TO FLOOR DRAIN. SHOW PIPING ON THE |
| | FLOOR PLAN, WITH ALL PIPE SIZE, VENTING, |
| | TRAPS. SECTION 106.1.1. |
| | 24. SHT P2.5 INDICATE THE LOCATION OF |
| | THE SECONDARY DRAINS FOR THE AREAS |
| | OUTSIDE UNITS T05 THRU T08. SUBMIT |
| | CALCULATION FOR PRIMARY AND SECONDARY |
| | DRAINS PER SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTION. SHOW AREA TO BE DRAINED FOR |
| | EACH AREA DRAIN, AND SHOW 1/2 AREA OF |
| | ALL VERTICAL WALL INCLUDING PARAPETS TO |
| | EACH AREA. IF SECONDARY DRAINS ARE |
| | SCUPPERS, INDICATE THAT THE SIZE OF THE |
| | SCUPPERS HAVE BEEN CALCULATED PER |
| | SECTIONS 1101.7, 1107.3 AND TABLE |
| | 1106.7. THE SIZING OF THE SCUPPERS CAN |
| | NOT BE DETERMINED WITHOUT REFERENCE TO |
| | THE DEFLECTION OF THE ROOF. |
| | 25. SHT P2.6 RWL'S ARE NOT IDENTIFIED IN |
| | COLS. OUTSIDE UNIT T03. SECTION 106.1.1. |
| | 26. SHT P2.16 AREA DRAINS OUTSIDE UNITS |
| | P02 AND P04 INDICATE PIPING DROPING TO |
| | THE 15TH FLOOR, BUT NO RWL SHOWN ON THE |
| | 15TH FLOOR. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | 27. SHT P2.16 INDICATE THE LOCATION OF |
| | THE SECONDARY DRAINS FOR THE AREAS |
| | OUTSIDE UNITS P02 THRU P04. SUBMIT |
| | CALCULATION FOR PRIMARY AND SECONDARY |
| | DRAINS PER SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTION. SHOW AREA TO BE DRAINED FOR |
| | EACH AREA DRAIN, AND SHOW 1/2 AREA OF |
| | ALL VERTICAL WALL INCLUDING PARAPETS TO |
| | EACH AREA. IF SECONDARY DRAINS ARE |
| | SCUPPERS, INDICATE THAT THE SIZE OF THE |
| | SCUPPERS HAVE BEEN CALCULATED PER |
| | SECTIONS 1101.7, 1107.3 AND TABLE |
| | 1106.7. THE SIZING OF THE SCUPPERS CAN |
| | NOT BE DETERMINED WITHOUT REFERENCE TO |
| | THE DEFLECTION OF THE ROOF. |
| | 28. SHT P2.22 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. IF SECONDARY ROOF DRAIN ARE |
| | SCUPPERS, THEY WILL BE SIZED PER |
| | SECTIONS 1101.7, 1107.3, AND TABLE |
| | 1106.7. |
| | 29. SHT P2.22 FLOOR DRAIN AT COOLING |
| | TOWERS IS NOT AN APPROVED INDIRECT WASTE |
| | RECEPTOR. SECTIONS 802.3 & 802.3.2. |
| | FLOOR SINK OR HUB DRAIN REQUIRED. |
| | RECEPTOR SHALL BE LOCATED UNDER COOLING |
| | TOWER TO PREVENT STORM WATER FROM |
| | ENTERING. |
| | 30. SHT P2.23 SHOW THE LOCATION OF ALL |
| | THE PRIMARY AND SECONDARY ROOF DRAINS. |
| | SUBMIT CALCULATION FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE AREA OF |
| | EACH DRAIN AND INDICATE 1/2 AREA OF ALL |
| | VERTICLE WALLS INCLUDING PARAPETS IN |
| | CALCULATION. IF SECONDARY DRAINS ARE |
| | SCUPPERS, THEY SHALL BE SIZED PER |
| | SECTIONS 1101.7, 1107.3 AND TABLE |
| | 1106.7. |
| | 31. SHT P2.24 SUBMIT CALCULATION FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTION 1106 & 1107 WITH ALL |
| | SUBSECTIONS. SHOW AREA OF EACH DRAIN AND |
| | SHOW 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS FOR EACH AREA IN |
| | CALCULATIONS. |
| | 32. SHT P3.1 DETAIL #03 RISER #33 SHALL |
| | NOT DRAIN THROUGH THE WET VENT FOR THE |
| | BATHROOM FIXTURES.ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | 33. SHT P4.1 SUBMIT A WATER RISER |
| | DIAGRAM TO REFLECT THE PIPING FOR THE |
| | 1ST AND 2ND FLOORS. SECTION 106.3.5.1.3. |
| | SHOW ALL PIPE SIZES, VALVES, ETC. |
| | 34. SHT P4.3 GAS RISER DIAGRAM. THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR |
| | SEPARATE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DEAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS. SOME SECTIONS DO NOT INDICAT |
| | THE LENGTHS. (SEE HIGHLIGHTED SECTIONS |
| | ON ONE SET OF PLANS) |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING IF USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTIONS 502 THRU 505. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | 35. SHT P4.3 DETIAL 01 INDICATES A |
| | TYPICAL BASE OF STACK SOVENT. THIS IS |
| | NOT TYPICAL OF ANY BASE OF STACK FOR THE |
| | SOVENT SYSTEM. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | 36. SHT P4.4 DETAIL 04 DOES NOT REFLECT |
| | THE FLOOR PLAN FOR THE WATER PIPING TO |
| | THE SHOWER AND TUB. NO DROPS FOR TUB AND |
| | SHOWER ARE SHOWN. PLEASE CORRELATE RISER |
| | AND FLOOR PLAN. SECTION 106.1.1. |
| | 37. SHT P4.4 DETAIL 05 SANITARY RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| | PLEASE CORRELATE THE RISER AND THE FLOOR |
| | PLAN. SECTION 106.1.1. |
| | 38. SHT P4.4 DETAIL 06 DOES NOT REFLECT |
| | THE FLOOR PLAN FOR THE WATER PIPING TO |
| | THE SHOWER AND TUB. NO DROPS FOR TUB AND |
| | SHOWER ARE SHOWN. PLEASE CORRELATE RISER |
| | AND FLOOR PLAN. SECTION 106.1.1. |
| | 39. SHT P4.4 DETAIL 07 DOES NOT REFLECT |
| | THE FLOOR PLAN. RISER SHOWS A TUB, BUT |
| | THE FLOOR PLAN SHOWS A SHOWER. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 106.1.1. |
| | 40. SHT P4.4 DETAIL 08 DOES NOT RELFECT |
| | THE FLOOR PLAN. RISER SHOWS A TUB, BUT |
| | THE FLOOR PLAN SHOWS A SHOWER. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 106.1.1. |
| | 41. SHT P4.5 DETAIL 06 DOES NOT REFLECT |
| | THE FLOOR PLAN. RISER SHOWS HOT & COLD |
| | STUBB OUTS ON THE DROP TO THE LAV AND |
| | SHOWER. PLEASE CORRELATE RISER AND THE |
| | FLOOR PLAN. SECTION 106.1.1. |
| | 42. SHT P4.7 SANITARY RISER DIAGRAM FOR |
| | THE SECOND FLOOR BATHROOM DOES NOT |
| | REFLECT THE FLOOR PLAN. FIRST W/C SHOWN |
| | PRIOR TO 4" SAN. DOWN ON THE FLOOR PLAN, |
| | BUT ON THE OTHER SIDE OF THE 4" SAN. |
| | DOWN ON THE RISER DIAGRAM. HDCP W/C FOR |
| | THE WOMEN'S TOILET ROOM IS NOT SHOWN ON |
| | THE RISER. PLEASE CORRELATE THE RISER |
| | AND THE FLOOR PLAN. SECTION 106.1.1. |
| | 43. SHT P4.7 DETAIL 02 SANT. RISER |
| | DIAGRAM FOR 2ND FLOOR PLAN. AIR |
| | ADMITTENCE VALVES ARE NOT APPROVED AS |
| | SHOWN. SEE SECTIONS 917.3.1 AND 917.3.2 |
| | 917.3.1 LOCATION OF BRANCH. |
| | THE HORIZONTAL BRANCH DRAIN SHALL |
| | CONNECT TO THE DRAINAGE STACK OR |
| | BUILDING DRAIN A MAXIMUM OF FOUR BRANCH |
| | INTERVALS FROM THE TOP OF THE STACK. |
| | 917.3.2 RELIEF VENT. |
| | THE HORIZONTAL BRANCH SHALL BE PROVIDED |
| | WITH A RELIEF VENT THAT SHALL CONNECT TO |
| | A VENT STACK, OR STACK VENT, OR EXTEND |
| | OUTDOORS TO THE OPEN AIR. THE RELIEF |
| | VENT SHALL CONNECT TO THE HORIZONTAL |
| | BRANCH DRAIN BETWEEN THE STACK OR |
| | BUILDING DRAIN AND THE MOST DOWNSTREAM |
| | FIXTURE DRAIN CONNECTED TO THE |
| | HORIZONTAL BRANCH DRAIN. THE RELIEF VENT |
| | SHALL BE SIZED IN ACCORDANCE WITH |
| | SECTION 916.2 AND INSTALLED IN |
| | ACCORDANCE WITH SECTION 905 . THE RELIEF |
| | VENT SHALL BE PERMITTED TO SERVE AS THE |
| | VENT FOR OTHER FIXTURE. |
| | 44. SHT P4.7 DETAIL 01 SANT. RISER |
| | DIAGRAM COLLECTION DOES NOT REFLECT THE |
| | FLOOR PLAN. RISER SHOWS 10"(1600FU), BUT |
| | THE FLOOR PLAN SHOWS 8"(1000FU). THE |
| | BASE OF STACKS P/1, P/3, P/5, 9/7 DOES |
| | NOT REFLECT THE FLOOR PLAN FOR THE PRL |
| | PIPING. THE RISER DOES NOT SHOW THE |
| | CONNECTION FOR THE 5" COMBINATION |
| | WASTE/VENT STACK (NOTE 33). PLEASE |
| | CORRELATE INFORMATION ON THE RISERS AND |
| | THE FLOOR PLAN. SECTION 106.1.1. |
| | 45. SHT P4.7 DETAIL 01 SANT. RISER |
| | DIAGRAM COLLECTION AIR ADMITTENCE VALVES |
| | ARE NOT APPROVED.SECTIONS 917.3.2 AND |
| | 917.3.2. |
| | 46. SHT P4.7 DETAIL 01 SANT. RISER |
| | DIAGRAM COLLECTION, PLEASE INDICATE |
| | WHERE THE CONTINUATION OF THE 2" UP TO |
| | SINK ON THE SECOND FLOOR IS LOCATED. |
| | SHOW PIPE SIZE, VENTING ETC. SECTION |
| | 106.1.1. |
| | 47. SHT P4.7 DETAILS 01 & 02 SHOW ALL |
| | PIPE SIZES OF ALL SECTIONS OF PIPE AND |
| | SHOW THE DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. TABLES 710.1(1) & 710.1(2). |
| | 48. SHT P5.1 DETAIL 08 PLEASE INDICATE |
| | CONDENSATE DRAIN FOR CONDENSATE. |
| | CONDENSATE SHALL NOT CONNECT TO SANITARY |
| | PER MUNICIPAL CODE SECTION 90-125(5). |
| | CONDENSATE SHALL BE PIPED OUT OF THE |
| | BUILDING SEPARATELY AND CONNECT TO THE |
| | STORM, CATCH BASIN, OR A DRYWELL. IF ITS |
| | A ROOF UNIT, IT CAN DRAIN TO A ROOF |
| | DRAIN. PLEASE CLARIFY.SECTION 106.1.1. |
| | 49. SHT P5.2 DETAIL 01 DOES NOT REFLECT |
| | ANY BASE OF STACKS SHOWN ON THE FLOOR |
| | PLAN. PLEASE CORRLEATE WITH FLOOR PLAN. |
| | SECTION 106.1.1. |
| | 50. SHT P5.2 DETAIL 06 FILTER FOR THE |
| | ICE MACHINE SHALL COMPLY WITH NSF 42. |
| | PLEASE SUBMIT MANUF. SPECIFICATION |
| | SHEETS. SECTION 611.1 |
| | 51. SUBMIT A WATER RISER DIAGRAM TO |
| | REFLECT THE PIPING FOR THE 1ST AND 2ND |
| | FLOORS. SECTION 106.3.5.1.3. |
| | 52. SUBMIT A WATER RISER DIAGRAM T0 |
| | REFLECT THE PIPING ON THE 14 TH & 15TH |
| | FLOORS. SECTION 106.3.5.1.3. |
| | 53. SUBMIT A GREASE WASTE ISOMETRIC |
| | RISER DIAGRAM. SECTION 106.3.5.1.3. |
| | 54. SUBMIT A BUILDING STORM ISOMETRIC |
| | RISER DIAGRAM SHOWING ALL PIPE SIZES, |
| | RWL CONNECTIONS AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM, AS WELL AS |
| | VERTICAL STORM RISERS. SECTION |
| | 106.1.5.1.3. |
| | 55. GREASE INTERCEPTORS SHALL BE SIZED |
| | BY LYNN MASSON ENVIRONMENTAL COMPLIANCE |
| | MANAGER. CONTACT HER AT (561) 822-2271, |
| | OR BY FAX (561) 772-2279, OR BY E-MAIL |
| | [email protected]. SUBMIT THE |
| | DETERMINATION SHEET FOR REVIEW WHEN |
| | RESUBMITTING PLANS REVIEW IN |
| | CONSTRUCTION SERVICES. WASTER ORD. 3434. |
| | 57. SUBMIT THE DESIGN MANUAL FOR THE |
| | SOVENT SYSTEM. THIS IS REQUIRED TO MAKE |
| | SURE ALL CRITERIA FOR THE SYSTEM IS |
| | BEING MET. SECTION 106.1.1. |
| | 58. PLANS DO NOT SEEM TO BE COMPLETE |
| | THIS REVIEW AND MORE COMMENTS WILL BE |
| | FOUTHCOMING WHEN PLANS ARE RESUBMITTED |
| | AS MORE INFORMATION IS AVAILABLE AND |
| | ACCORDING TO THE RESPONSE FROM THIS |
| | REVIEW. |
| | 59. SHTS A6.1.1 THRU A6.14.2 ALL |
| | ACCESSIBLE BATHROOMS. SOME UNITS |
| | INDICATE THAT THE SHOWER IS NOT AN ADA |
| | ACCESSIBLE PLUMBING FIXTURE. ALL SHOWERS |
| | PROVIDED IN ACCESSIBLE UNITS SHALL BE |
| | ACCESSIBLE PER SECTION 11-4.21. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.21 AND ALL SUBSECTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE SUBMIT THE HIGHLIGHTED SET OF |
| | PLUMBING PLANS FROM FIRST REVIEW FOR |
| | COMPARISON TO HELP EXPEDITE THE SECOND |
| | REVIEW. |
| | |