| Date |
Text |
| 2006-03-24 00:00:00 | DENIED: |
| | 1.PLAN SHEET M0.1 MECHANICAL CODES, |
| | PLEASE NOTE, THE FOLLOWING CODES SHOULD |
| | READ AS FOLLOWS: NFPA 90A-2002, NFPA |
| | 90B-2002. |
| | |
| | 2.PLAN SHEET M2.1 EXHAUST FROM THE |
| | FIRE PUMP ROOM & THE TRASH ROOM |
| | TERMINATE OVER THE DOOR AREA.PER 2004 |
| | FMC 401.5 EXHAUST OPENINGS SHALL BE |
| | LOCATED A MINIMUM OF 10 FT FROM LOT |
| | LINES.WHERE OPENINGS FRONT ON A STREET |
| | OR PUBLIC WAY, THE DISTANCE SHALL BE |
| | MEASURED TO THE CENTERLINE OF THE STREET |
| | OR PUBLIC WAY.PER 2004 FMC 401.5.2 |
| | OUTDOOR EXHAUST AIR SHALL NOT BE |
| | DIRECTED ONTO WALKWAYS OR CREATE A |
| | NUISANCE. |
| | |
| | 3.PLAN SHEET M2.1 FRESH AIR INTAKE |
| | SHALL COMPLY WITH 2004 FMC 401.5 & |
| | 410.5.1. |
| | |
| | 4.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2004 FMC |
| | TABLE 403.3.PROVIDE CALCUALTIONS FOR |
| | ALL COMMON, RESIDENTIAL, AND GARAGE |
| | AREAS. |
| | |
| | 5.PLAN SHEET M2.2 EXHAUST TERMINATING |
| | FROM THE TRASH & RESTROOMS.PLEASE |
| | NOTE, THE TERMINATION IS BELOW A BALCONY |
| | WITH SLIDING GLASS DOORS. |
| | |
| | 6.PLEASE CLARIFY RATING OF THE |
| | SEPARATION WALL BETWEEN THE TRASHOLD (RM |
| | 218) & THE DIRECTOR OF SALES (RM 221). |
| | SHOW COMPLIANCE WITH NFPA 82-1999 |
| | CHAPTER 3 SUB-SECTION 3-2.3. FIRE |
| | DAMPERS ARE NOT REQUIRED IN AREAS WHERE |
| | THE DUCT COMPLIES WITH 2004 FMC 607.5.3 |
| | EXCEPTION #2 ITEMS 2.1 THROUGH 2.6. |
| | PLEASE ANNOTATE ON PLAN THE LOCATIONS |
| | THAT THIS WILL APPLY. |
| | |
| | 7.PLAN SHEET M2.2 CLARIFY THE LINEN |
| | STORAGE AREA, INDICATE IF A LAUNDRY |
| | CHUTE WILL BE INSTALLED. |
| | |
| | 8.PLEASE NOTE, LINEN & TRASH CHUTES |
| | SHALL COMPLY WITH NFPA 82-1999 CHAPTER 3 |
| | SUB-SECTION 3-2.5.1, WHICH REQUIRES |
| | AUTOMATIC SPRINKLERS. |
| | |
| | 9.PLAN SHEET M2.3, PLEASE INDICATE |
| | WHERE THE MAKE-UP AIR WILL COME FROM FOR |
| | THE GARAGE VENTILATION. |
| | |
| | 10. PLANS FOR PARKING AREA (M2.3 & M2.4) |
| | DO NOT INDICATE WHERE THE CO SENOSRS |
| | WILL BE SET.PER 2004 FMC 404.1, THE |
| | ACTIVATION OF THE GARAGE EXHAUST BY |
| | CARBON MONOXIDE SENSORS SHALL BE AT A |
| | CONSENTRATION LEVEL NOT GREATER THAN |
| | 25PPM. PLEASE INDICATE HOW THE SENSORS |
| | WILL BE TESTED. |
| | |
| | 11. PLAN SHEET M2.5, M2.6, M2.16, & |
| | M2.17 INDICATE FIRE DAMPERS ON THE |
| | SUPPLY AND SMOKE EXHAUST DUCTS FOR THE |
| | COMMON AREAS. ACCORDING TO THE LEGEND ON |
| | PLAN SHEET M0.1 FIRE DAMPERS ARE THE |
| | ONLY DAMPERS INDICATED ON THE PLANS. |
| | PLAN SHEET M5.3, INDICATES THE FIRE |
| | DAMPERS DEPICTED ON THE PLANS SHOULD |
| | ACTUALLY BE COMBINATION FIRE/SMOKE |
| | DAMPERS.PLEASE VERIFY AND CORRELATE |
| | WITH SMOKE CONTROL SYSTEM.PLEASE |
| | INDICATE THE CORRECT SYMBOL AS INDICATED |
| | UNDER THE "MECHANICAL SYMBOLS" DEPICTED |
| | ON PLAN SHEET M0.1. |
| | |
| | 12. PLAN SHEET M2.5, PLEASE CLARIFY THE |
| | SUPPLY AIR FROM AHU-1 WHICH SERVES THE |
| | CORRIDOR.IS THE INTENT OF THIS FOR |
| | COMPLIANCE WITH THE OUTSIDE AIR |
| | REQUIREMENTS OF 2004 FMC TABLE 403.3? |
| | |
| | 13. PLAN SHEET M2.5 UNIT 503, PLEASE |
| | INDICATE LOCATION OF THE RETURN AIR BACK |
| | TO FCU-V5. |
| | |
| | 14. PLAN SHEET M2.5, M2.6, M2.16, & |
| | M2.17 PLEASE INDICATE DUCT, GRILLE SIZE |
| | & CFM FOR THE SUPPLY DUCT TO THE |
| | BATHROOM AREAS. |
| | |
| | 15. PLEASE NOTE DEPENDING ON THE |
| | RESPONSE TO ITEM 14 R/A TRANSFER GRILLS |
| | MAY NOT BE SIZED LARGE ENOUGH. |
| | |
| | 16. PLAN SHEET M2.21 KEY NOTE 1 |
| | REFERENCES DETAIL 07 ON PLAN SHEET M8.1. |
| | PLAN SHEET M8.1 WAS NOT SUBMITTED FOR |
| | REVIEW. |
| | |
| | 17. PLAN SHEET M2.1 KEY NOTE 3 "RISER |
| | SIZE EQUAL TO VERTICAL RUN".PLEASE |
| | CLARIFY, "RISER SIZE EQUAL TO VERTICAL |
| | RUN", A RISER IS A VERTICAL RUN.SHOULD |
| | THIS READ, "RISER SIZE EQUAL TO |
| | HORIZONTAL RUN"? |
| | |
| | 18. PLEASE SIZE ALL DUCTWORK AND PIPING. |
| | |
| | 19. PLEASE PROVIDE ADDTIONAL INFORMATION |
| | ABOUT THE MECHANICAL ROOMS LOCATED ON |
| | THE ROOF (GENERATOR, AHU, PUMP COOLING |
| | TOWERS).ARE THESE AREAS ENCLOSED? |
| | PLEASE PROVIDE INFORMATION ON THE |
| | VENTILATION OF THESE AREAS SHOULD THEY |
| | BE ENCLOSED. |
| | |
| | 20. PROVIDE ENERGY AND MANUAL J |
| | CALCULATIONS IN ACCORDIANCE WTIH 2004 |
| | FBC CHAPTER 13. |
| | |
| | 21. PLEASE PROVIDE SUBMITTALS FOR ALL |
| | EQUIPMENT & APPLIANCES. |
| | |
| | 22. PLEASE PROVIDE FILL INFORMATION FOR |
| | THE EMERGENCY GENERATOR. |
| | |