| Date |
Text |
| 2006-04-28 00:00:00 | ******DENIED****** |
| | |
| | 1) FIRE DEPARTMENT CONNECTIONS SHALL BE |
| | LOCATED NO FURTHER THAN 150' FROM A FIRE |
| | HYDRANT. |
| | |
| | 2) BUILDING SHALL MEET ALL REQUIREMENTS |
| | FOR HIGHRISE STRUCTURES IN ACCORDANCE |
| | WITH APPLICABLE BUILDING CODES, AND NFPA |
| | 101, CHAPTER 11. |
| | |
| | 3) IN ADDITION TO ELECTRONIC |
| | SUPERVISION, DOUBLE CHECK DETECTOR |
| | ASSEMBLY SHALL BE SECURED WITH CHAIN AND |
| | LOCK. |
| | |
| | 4) LIFE SAFETY SHALL COMPLY WITH NFPA |
| | 101, 2003 EDITION. |
| | |
| | 5) INCORRECT CODE EDITIONS ARE |
| | REFERENCED ON SHT M0.1. AS PART OF LIFE |
| | SAFETY, MEANS OF EGRESS TO COMPLY WITH |
| | NFPA 101, 2003 EDITION. NFPA 13, AND |
| | NFPA 72, 2002 EDITIONS SHALL BE |
| | REFERENCED. |
| | |
| | 6) PLEASE VERIFY THE WIDTH OF DOOR 100B |
| | THAT ENTERS THE LOBBY. |
| | |
| | 7) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN BUILDING REACHES (3) STORIES OR 30' |
| | IN HEIGHT. |
| | |
| | 8) STANDPIPE CONNECTIONS TO BE 2 1/2"- 1 |
| | 1/2" REDUCER WITH CHAINS. |
| | |
| | 9) WARNING SIGNS ARE REQUIRED IN |
| | ELEVATOR LOBBIES. |
| | |
| | 10) PLEASE INDICATE ALL ELEVATORS THAT |
| | ARE STRETCHER ACCESSIBLE. |
| | |
| | 11) SIGNS SHALL BE PROVIDED IN ALL |
| | STAIRWELLS INDICATING TOP, BOTTOM, FLOOR |
| | IDENTITY AND ROOF ACCESS. |
| | |
| | 12) NO CUTTING OR WELDING OPERATIONS ARE |
| | PERMITTED WITHOUT APPROVAL OF THE BUREAU |
| | OF FIRE PREVENTION AND COMPLIANCE WITH |
| | NFPA 51B. |
| | |
| | 13) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR HANDRAILS AND GUARDS. |
| | |
| | 14) IS THERE A DOOR LOCATED AT THE |
| | BOTTOM OF STAIR #1 AT EXIT CORRIDOR 112? |
| | |
| | THERE IS NOT ONE SHOWN. |
| | |
| | 15) PLEASE PROVIDE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS IN TERMS OF CLASS A,B OR C. |
| | |
| | 16) THE PARKING GARAGE SHALL COMPLY WITH |
| | APPLICABLE BUILDING CODES AND NFPA 88A. |
| | |
| | 17) STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 18) PLEASE INDICATE THE QUANTITY AND |
| | TYPE OF CONTENTS THAT WILL BE STORED IN |
| | POOL EQUIPMENT ROOM. |
| | |
| | 19) COOLING TOWERS SHALL COMPLY WITH |
| | NFPA 214. |
| | |
| | 20) NO STORAGE ALLOWED IN ELECTRICAL OR |
| | MECHANICAL EQUIPMENT ROOMS THAT ARE |
| | SUBJECT TO SERVICING AND INSPECTIONS. |
| | |
| | 21) PLEASE INDICATE ON PLANS REGARDING |
| | POOL DECK AREA TO BE SLIP RESISTANT. IN |
| | ADDITION, PROVIDE OCCUPANT LOAD FOR SAME |
| | AREA. |
| | |
| | 22) ADDRESS IS REQUIRED ON BUILDING. |
| | PLEASE ILLUSTRATE OF PROVIDE NOTE TO |
| | THIS EFFECT ON ELEVATION SHEETS. |
| | |
| | 23) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. JOB |
| | SITE SHALL BE CLEANED OF DEBRIS DAILY. |
| | |
| | 24) SOFFITS SHALL NOT INTERFERE WITH |
| | FIRE PROTECTION EQUIPMENT OR DEVICES. |
| | |
| | 25) FIRE EXTINGUISHER CABINETS SHALL BE |
| | INSTALLED AT DISTANCES NOT TO EXCEED 75' |
| | TRAVEL DISTANCE. |
| | |
| | 26) NO MENTION ON DOOR SCHEDULES |
| | REGARDING UL CERTIFIED CLOSERS ON RATED |
| | DOORS. |
| | |
| | 27) ELEVATORS TO COMPLY WITH ASME A17.1. |
| | |
| | 28) PLEASE PROVIDE ADDITIONAL |
| | INFORMATION AND CUT SHEETS FOR CO |
| | SENSORS IN PARKING GARAGE AREAS. |
| | |
| | 29) DUCT SMOKE DETECTORS SHALL INITIATE |
| | A GENERAL FIRE ALARM IN ACCORDANCE WITH |
| | LOCAL REQUIREMENTS. |
| | |
| | 30) PLEASE ADD THE STACK EFFECT WORDING |
| | TO THE MECHANICAL PLANS. |
| | |
| | 31) PLEASE CORRECT CODE EDITIONS ON ALL |
| | SHEETS. |
| | |
| | 32) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 33) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE PUMP, FUEL AND |
| | ASSOCIATED EQUIPMENT. |
| | |
| | 34) PLEASE PROVIDE INFORMATION THAT |
| | WOULD SUPPORT THE APPROVAL OF A 750 GPM |
| | FIRE PUMP SERVICING A 21 STORY BUILDING. |
| | |
| | |
| | 35) BUILDING SHALL BE FULLY FIRE |
| | SPRINKLER PROTECTED. ANY AREAS NOT PART |
| | OF THIS SCOPE OF WORK MAY REQUIRE |
| | REMODEL ONCE OCCUPIED BY FUTURE TENANT. |
| | |
| | 36) PLEASE INCLUDE LIFE SAFETY SHEETS TO |
| | ILLUSTRATE ALL ASPECTS OF MEANS OF |
| | EGRESS INCLUDING MAXIMUM TRAVEL |
| | DISTANCES. |
| | |
| | 37) PLEASE INCLUDE THE FIRE SPRINKLER |
| | LAYOUT FOR TRASH AND LAUNDRY CHUTES. |
| | |
| | 38) FIRE ALARM SYSTEM SHALL BE UL |
| | CERTIFIED FOR CENTRAL STATION SERVICE. |
| | CERTIFICATE OR APPROVED COPY OF SUCH |
| | SHALL BE AVAILABLE PRIOR TO OR AT THE |
| | TIME OF FIRE ALARM FINAL. |
| | |
| | 39) FIRE DEPARTMENT CONNECTIONS ARE |
| | BEING SHOWN ON THE BUILDING AND FIRE |
| | BACK FLOW PREVENTER ON FP 4.1. ARE THERE |
| | A TOTAL OF (3) CONNECTIONS? |
| | |
| | 40) FIRE ALARM SYSTEM TO MEET THE NFPA |
| | 72 REQUIREMENTS FOR SURVIVABILITY. |
| | |
| | 41) PLANS DON'T APPEAR TO SHOW COMPLETE |
| | FIRE ALARM EQUIPMENT LAYOUT ON |
| | ELECTRICAL SHEETS. |
| | |
| | 42) SMOKE DETECTORS IN LIVING UNITS ARE |
| | REQUIRED TO BE SINGLE STATION TYPE. ALL |
| | OTHER DEVICES SHALL BE TIED INTO THE |
| | FIRE ALARM SYSTEM. |
| | |
| | 43) PLEASE PROVIDE FURTHER |
| | INFORMATION/CUT SHEETS FOR SMOKE GUARD |
| | SHUTTERS THAT ARE TIED INTO FIRE ALARM |
| | SYSTEM. |
| | |
| | 44) THE GENERATOR SHALL COMPLY WITH NFPA |
| | 110, STANDARD FOR EMERGENCY AND STANDBY |
| | POWER SYSTEMS. |
| | |
| | 45) SMOKE DETECTORS SHALL BE LOCATED A |
| | MINIMUM OF (3)' FROM HVAC DIFFUSERS. |
| | |
| | 46) FIRE ALARM SYSSTEM SHALL BE CLASS A |
| | OR FULLY ADDRESSABLE. |
| | |
| | 47) ALL SHAFTS THAT ARE LARGE ENOUGH FOR |
| | PERSONS TO FALL INTO MUST BE MARKED |
| | SHAFTWAY IN "6" IN CHARACTERS. |
| | |
| | 48) ALL FIRE DOORS/WINDOWS TO COMPLY |
| | WITH NFPA 80. PLEASE ADD NOTE TO PLANS. |
| | |
| | 49) EXITS SIGNS SHALL BE LOCATED AT |
| | DISTANCES NOT TO EXCEED 100'. |
| | |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |