| 2006-04-10 00:00:00 | IN REVIEW |
| | ******** UNSAT ********** |
| | |
| | THE HARRICKHOTEL / CONDO |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE TO REFERENCE ALL |
| | THE CURRENT CODE IN EFFECT AS FOLLOWS. |
| | NFPA-20 (2002), NFPA-110 (2002). OTHERS |
| | ARE SHOWN CURRENT TO DATE. |
| | |
| | 2) NOTE: PLEASE SEE "KEY NOTES" ON E1.1, |
| | #4 SEEMS TO BE #1, AND #1 SEEMS TO BE |
| | IDENTIFIED IN TWO LOCATIONS? PLEASE |
| | CORRELATE. |
| | |
| | 3) NOTE: PLEASE CLARIFY AREAS INCLUDING |
| | FIRST FLOOR WHICH MENTIONS A FUTURE |
| | TENANT BUILD OUT YET, THIS ARE SEEMS TO |
| | BE THE LOBBY AREA OF THE HOTEL/ CONDO. |
| | HOW IS THIS TENANT BLD OUT? |
| | |
| | 4) NOTE: PLEASE PROVIDE ALL ROOM AND |
| | AREA DESIGNATIONS ON PLANS. |
| | PLEASE ALSO PROVIDE ALL AREA AND ROOM |
| | DESIGNATIONS FOR UNITS AS SOME CODE |
| | COMPLIANCE ITEMS CAN NOT BE VERIFIED AT |
| | THIS TIME. |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE CORRELATE ALL DOORS FOR |
| | ELECTRICAL ROOMS FOR OUT SWING. PLEASE |
| | SEE ELECTRICAL PLANS INDICATE THE |
| | CORRECT OUT-SWING FOR MAIN ELECTRICAL |
| | ROOM; HOWEVER ARCHITECTURAL PLANS SHOW |
| | DOORS SWINGING INWARDS. |
| | PLEASE ALSO PLACE NOTE ON PLANS FOR |
| | REQUIRED PANIC HARDWARE. |
| | 110.26 |
| | PLEASE ALSO SEE ANY INTERFERENCE WITH |
| | MINIMUM WIDTHS AND EGRESS PATHS WHICH |
| | MAY BE AFFECTED. |
| | PLEASE PROVIDE NOTE FOR PANIC HARDWARE |
| | WHICH WILL BE REQUIRED. |
| | 6) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM |
| | SHALL CONTAIN TWICE THE CLEARANCES |
| | REQUIRED PER 110.26 FOR ATS EQUIPMENT |
| | PER NFPA-110 7.2.2.1. |
| | THIS WILL AFFECT LAYOUT AS SHOWN. |
| | |
| | 7) NOTE: PLEASE SEE 6.24* FOR MANUAL |
| | MEANS OF DISCONNECT REQUIRED FOR ATS |
| | DEVICES. |
| | CAN NOT VERIFY AT THIS TIME. |
| | |
| | 8) NOTE: PLEASE SEE 7.2.1.1 FOR MIN 2HR |
| | RATINGS FOR EPSS EQUIPMENT. NFPA-110 |
| | |
| | 9) NOTE: PLEASE SEE COLOR CODING OF |
| | 277/480V SYSTEMS SHALL BE "BROWN, |
| | PURPLE, AND YELLOW". ORANGE IS ONLY FOR |
| | HIGH-LEG SYSTEMS AND IS NOT PERMITTED |
| | FOR 277/480V. |
| | 215, 90.4. |
| | |
| | 10) NOTE: PLEASE KNOW, "LIGHTNING |
| | PROTECTION"SYSTEM AS SHOWN IF |
| | INSTALLED BY A SUB CONTRACTOR WILL |
| | REQUIRED THIS TO BE PULLED UNDER A |
| | SEPARATE PERMIT. |
| | |
| | 11) NOTE: PLEASE SEE NFPA-1107.3.3* |
| | THE INTENSITY OF ILLUMINATION IN THE |
| | ROOM HOUSING THE EPS EQUIPMENT FOR LEVEL |
| | 1 SHALL BE 32.3 LUX (30 FT-CANDLES). |
| | PLEASE SHOW DETAIL. |
| | |
| | 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR |
| | ALL EPS EQUIPMENT. (ATS). PLEASE SEE |
| | 6.5.2 NFPA-110. |
| | UNABLE TO VERIFY AT THIS TIME. |
| | |
| | 13) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR ALL EQUIPMENT: |
| | ATS'S, GENERATOR, FIRE PUMP FIRE PUMP |
| | CONTROLLER, SUB-BASE FUEL TANK ETC. |
| | PLEASE SEE OTHER COMMENTS AND KNOW THAT |
| | MANY ITEMS FOR CODE COMPLIANCE CAN NOT |
| | BE REVIEW AT THIS TIME DUE TO THESE |
| | ITEMS NOT BEING SUBMITTED FOR REVIEW. |
| | |
| | |
| | |
| | 14) NOTE: PLEASE SEE NFPA-20 7.2FOR |
| | LOCATION OF FP CONTROLLER, HEIGHT, NEMA |
| | TYPE 2 ENCLOSURES AND ROOM CONTAINING A |
| | FLOOR DRAIN. |
| | |
| | 15) NOTE:PLEASE NOTE ON PLANS THE |
| | ACCEPTANCE OF THE EPS AS REQUIRED IN |
| | NFPA-110 7.13. |
| | |
| | |
| | 16) NOTE: PLEASE PROVIDE NOTE ON PLANS |
| | WHICH PROHIBITS THE INSTALLATION OF ANY |
| | ELECTRICAL CONDUITS ETC IN STAIRS UNLESS |
| | SPECIFICALLY DESIGNATED TO THE STAIRS. |
| | PLEASE ALSO PROVIDE NOTE FOR ELEVATOR |
| | EQUIPMENT ROOMS. |
| | 215.5 |
| | |
| | |
| | 17) NOTE: PLEASE SUBMIT WIND LOAD |
| | CALCULATIONS FOR ALL SITE LIGHTING POLES |
| | INCLUSIVE OF ATTACHED LIGHT FIXTURES. |
| | PLEASE KNOW, THIS SHOULD INCLUDE ANY |
| | POLE FIXTURES ON POOL DECK/ROOF |
| | LEVEL(S). |
| | THESE CALCULATIONS WHICH ARE REQUIRED AT |
| | THIS TIME SHALL MEET THE 2004 FBC WITH |
| | RESPECT TO WIND PRESSURES AND DESIGNS |
| | 140 MPH. |
| | |
| | 18) NOTE: PLEASE SEE GFI PROTECTION |
| | REQUIRED IN POOL AREAS FOR CIRCUITS |
| | EE22-26., PL-22 /27 |
| | |
| | 19) NOTE: PLEASE SEE FIXTURES ON FIXTURE |
| | SCHEDULE WHICH INDICATE 120V TYPE |
| | FIXTURES IN POOL AREAS, YET THESE ARE |
| | CIRCUITED TO THE 277/480V PANELS?? |
| | PLEASE SEE THE CODE DOES NOT SEE TO |
| | PROVIDE COMMENTARY FOR ALLOWING 277/480V |
| | LIGHTING IN CLOSE PROXIMITY TO POOL |
| | AREAS. |
| | PLEASE VERIFY FIXTURES TYPES AND |
| | VOLTAGES AND ADJUST PLANS AND SCHEDULES |
| | AS NEEDED. |
| | 680, 215.5. |
| | |
| | 20) NOTE: PLEASE SEE NOTE TO BE PROVIDED |
| | ON ALL E-2.09AB FOR MINIMUM CLEARANCES |
| | FOR POOL AREA FIXTURES. PLEASE 680.22 |
| | FOR HIGH VOLTAGE FIXTURES (5FT MIN W/ |
| | GFI PROTECTION AND 10FT MIN FOR LOW |
| | VOLTAGE TYPE FIXTURES. 411.4 |
| | |
| | |
| | 21) NOTE: PLEASE SEE FIXTURE AS T-1 |
| | SHOWN IN FIRE PUMP ROOM COULD NOT BE |
| | LOCATED ON SCHEDULE. PLEASE KNOW AND |
| | BATTERY BACK UP FIXTURE OF SOME SORT |
| | WILL BE REQUIRED. THIS FIXTURE AS SHOWN |
| | SEEMS TO BE SHADED WHICH LENDS |
| | IDENTIFICATION TO MANY OTHER FIXTURES ON |
| | PLANS WHICH ARE SHADED AND ARE FIXTURES |
| | WITH BATTERY BACK UP. |
| | NFPA-20, LS 101 NFPA-70 |
| | |
| | 22) NOTE:PLEASE SEE NFPA-20.6.2.2 |
| | WHICH REQUIRES A MIN OF 8HRS RUNNING @ |
| | 100% LOAD FOR FIRE PUMP. PLEASE ALSO |
| | BEAR IN MIND THE MINIMUM 100% LOADS FOR |
| | ALL OTHER LEGALLY REQUIRED STAND-BY |
| | ITEMS |
| | |
| | 23) NOTE: PLEASE VERIFY POWER LAYOUT FOR |
| | FLOORS 1-4. 16-21 SHOWN ON E-2.16, AND |
| | 5-15, ? |
| | 215.5 |
| | |
| | 24) NOTE: PLEASE SEE 2.23 WHICH SEEM TO |
| | SHOW TWO DIFFERENT B-1 FIXTURES. PLEASE |
| | CORRELATE AND SEE ONE SHADED AND THE |
| | OTHER IS NOT. |
| | REDLINED AT LOCATION(S). |
| | |
| | 25) NOTE: PLEASE PROVIDE A BATTERY BACK |
| | FIXTURE OF SOME SORT IN ELEVATOR |
| | EQUIPMENT ROOMS. |
| | LS 101 7.8,7.9,700.16 |
| | |
| | 26) NOTE: PLEASE SEE E2.3, WHICH SHOWS |
| | WHAT APPEARS TO BE FCU LOCATED IN FRONT |
| | OFPANEL EH-3? |
| | PLEASE VERIFY IF UNIT IS CEILING |
| | MOUNTED? |
| | PLEASE SEE MANY OTHER UNITS IN |
| | ELECTRICAL ROOMS AND SPACES WHICH MAY |
| | NOT BE PERMITTED. |
| | 110.26 |
| | |
| | |
| | 27) NOTE: PLEASE SEE 620.22, 620.23, AND |
| | 620.24 FOR ALL MINIMUM REQUIRED |
| | DEDICATED BRANCH CIRCUITS. PLEASE SEE |
| | SOME APPEAR TO SHARE WITH OTHER AREAS |
| | BESIDES ONLY THE ELEVATOR EQUIPMENT |
| | ROOMS. |
| | ALL ROOMS SHALL CONTAIN THEIR OWN |
| | DEDICATED CIRCUITS AND MAY NOT FEED |
| | OTHER ROOMS OR OTHER COMMON AREAS. |
| | |
| | 28) NOTE: PLEASE SEE FIRE PUMP ROOM |
| | WHICH SHOWS A SYMBOL WHICH COULD NOT BE |
| | IDENTIFIED. THIS IS ALSO LOCATED IN ROOM |
| | ADJACENT TO FIRE PUMP ROOM. |
| | 215.5 |
| | |
| | 29) NOTE: PLEASE PROVIDE EMERGENCY |
| | LIGHTING FOR EGRESS TO THE PUBLIC RIGHT |
| | OF WAY. PLEASE SEE THE BREEZEWAY AREAS/ |
| | DRIVE AREA WHICH MAY BE USED AS AN |
| | EGRESS PATH WAY. |
| | LS 101-7.8,7.9 |
| | |
| | 30) NOTE: PLEASE SEE FBC 2004 CHAPTER 13 |
| | FOR MEANS OF CONTROL REQUIRED FOR |
| | EXTERIOR LIGHTING. PLEASE PROVIDE ANY |
| | AREA CALCULATIONS AS SET FORTH. |
| | 13-415.1.ABC.2 (IF APPLICABLE) |
| | |
| | 31) NOTE: PLEASE SEE 13-415.1.ABC.1.1 & |
| | .2 FOR CONTROL OF INTERIOR LIGHTS. |
| | PLEASE KNOW, ALL ROOMS NOT IN USE FOR |
| | 24HR OPERATION SHALL CONTAIN MEANS OF |
| | BEING AUTOMATICALLY TURNED OFF.PLEASE |
| | KNOW, THIS INCLUDES ANY STORAGE, |
| | MECHANICAL, CLOSETS ETC. |
| | PLEASE SEE OTHER NEW REQUIREMENTS OF |
| | CHAPTER 13. |
| | |
| | |
| | 32) NOTE:PLEASE PROVIDE COMPLETE |
| | PHOTO-METRICS FOR ALL CORRIDORS, EGRESS |
| | PATHS, STAIR TOWERS. |
| | PLEASE SEE 2003 NFPA-101 7.8 AND 7.9. |
| | THIS REQUIRES A MIN OF 10 FT CANDLES |
| | FOR STAIRS UNDER NORMAL POWER AND A |
| | MINIMUM OF 1 FT CANDLE UNDER EM POWER. |
| | PLEASE ALSO KNOW THAT BATTERY BACK UP |
| | FIXTURE IS ALREADY BEING SHOWN IN STAIR |
| | TOWERS. |
| | PLEASE KNOW THIS MAY BE A "TYPICAL" |
| | DETAIL FOR THESE AREAS.. PLEASE SEE |
| | OTHER AREAS BESIDES STAIRS SHALL BE |
| | PERMITTED TO PROVIDE 1FT CANDLE |
| | (AVERAGE) UNDER NORMAL AND EMERGENCY. |
| | |
| | 33) NOTE:PLEASE SEE THAT ANY AFTER |
| | DUSK BEFORE DAWN SWIMMING WILL REQUIRE |
| | PHOTO-METRICS FOR POOL AREA(S). PLEASE |
| | KNOW, ALL PHOTO-METRICS WILL BE REQUIRED |
| | TO BE SUBMITTED TO PALM BEACH COUNTY |
| | HEALTH DEPARTMENT FOR REVIEW AND |
| | STAMPING. ONLY THE STAMPED PLANS/SHEETS |
| | FROM PBCHD SHOULD BE SUBMITTED. |
| | |
| | 34) NOTE: PLEASE VERIFY SPECS FOR FIRE |
| | PUMP CONTROLLER. AS SHOWN THIS IS NOT AN |
| | ELECTRIC DRIVE UNITS, HOWEVER PLEASE SEE |
| | NFPA-20 AS THE MEANS OF DISCONNECTING IS |
| | REQUIRED ON THE OUTSIDE OF THE FIRE PUMP |
| | CONTROLLER. PLEASE SEE SPECS WERE NOT |
| | SUBMITTED AND UNABLE TO VERIFY THIS AT |
| | THIS TIME. |
| | |
| | 35)NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1 AND .2 WITH RESPECT TO |
| | DESIGN IF LIGHTING CONTROL WHICH NOT 24 |
| | HRS OF OPERATION, MEANS OF EGRESS OR FOR |
| | SECURITY PURPOSES. |
| | |
| | 36) NOTE: PLEASE PROVIDE VOLTAGE DROP |
| | ANALYSIS FOR ALL FEEDERS AND BRANCH |
| | CIRCUITS. THIS MAY BE A WORST CASE |
| | SCENARIO FOR EACH. |
| | THIS MAY ALSO BE NOTED. PLEASE SEE FBC |
| | CHAPTER 13, 13-413.1.ABC.1.1, &.2. |
| | PLEASE SEE RISER MENTIONS VD FOR |
| | FEEDERS, YET THIS IS BUS-DUCT. |
| | |
| | 37) NOTE: PLEASE SEE FAIR HOUSING ACT |
| | REGULATIONS, 24 CFR 100.205 WITH RESPECT |
| | TO HEIGHTS AND LOCATIONS FOR ALL |
| | ACCESSIBLE DEVICES. |
| | PLEASE PLACE NOTE ON PLANS FOR FHAR. |
| | |
| | 38) NOTE: PLEASE SEE LOCATION OF |
| | GENERATOR LOCATED ON ROOF TOP IS STILL |
| | IN REVIEW AND WILL BE GONE OVER WITH |
| | FIRE MARSHAL'S OFFICE FOR ANY |
| | DETERMINING FACTOR'S WHICH MAY AFFECT |
| | THE ELECTRICAL PLANS. |
| | PLEASE KNOW, AT THIS TIME, THE EDS2 WILL |
| | BE REQUIRED TO CONTAIN A MAIN, WITH A |
| | MANUAL MEANS OF DISCONNECT LOCATED ON |
| | THE OUTSIDE OF THE EQUIPMENT. THE |
| | BREAKER LOCATED AT THE ROOFTOP GEN |
| | SHOULD BE THE UNIT TO CONTAIN THE SHUNT |
| | TRIP BREAKER. PLEASE ALSO KNOW, A MEANS |
| | OF SHUTTING DOWN THE NATURAL GAS AND |
| | OTHER FUEL SUPPLY WILL BE REQUIRED. |
| | |
| | 39) NOTE: PLEASE SEE CODES WITH RESPECT |
| | TO LOCATIONS OF SMOKE DETECTORS. |
| | PLEASE SEE FIRE REVIEW COMMENTS AS THESE |
| | UNITS ARE ALSO TO BE CONDO UNITS |
| | CONTAINING COOKING FACILITIES, THE SD'S |
| | MAY NOT BE CONNECTED INTO THE MAIN |
| | BUILDING FA SYSTEM. PLEASE KNOW, IF THIS |
| | IS INDEED THE CASE THE SD'S WILL BE 120V |
| | BATTERY BACK UP AND CIRCUITED TO UNITS. |
| | THIS WILL AFFECT CIRCUITING AND INVOKE |
| | ARC FAULT PROTECTION. |
| | PLEASE SEE 2002 NFPA-72 11.5.1.1, |
| | 11.5.8.3.5. SD'S ARE TO BE LOCATED A MIN |
| | OF 3FT FROM KITCHEN AND BATH DOORS AND A |
| | MIN OF 20FT FROM COOKING APPLIANCES. |
| | (WITH EXCEPTIONS TO THE DISTANCE FROM |
| | COOKING APPLIANCES. |
| | PLEASE PLACE NOTES ON PLANS. |
| | |
| | |
| | 40) NOTE: PLEASE SEE 210.12 IN THE 2002 |
| | NEC WHICH REQUIRES ARC FAULT PROTECTION |
| | FOR ALL "OUTLETS" ( SD'S, LTS, FANS, |
| | RECEPTS ETC.)IN BEDROOMS. |
| | PLEASE SEE NOTES ON PLANS FOR ALL UNITS |
| | INDICATE PROTECTION FOR RECEPTS ONLY. |
| | PLEASE SEE 2002 NEC. |
| | |
| | |
| | 41) NOTE: PLEASE SEE 210.52 FOR |
| | RECEPTACLE SPACING INSIDE DWELLING UNITS |
| | FOR 2 FT, 6FT AND 12 FT RULE. |
| | PLEASE SEE UNIT LAYOUT AS MANY OF THESE |
| | HAVE BEEN REDLINED. |
| | |
| | 42) NOTE: PLEASE SEE PLANS SEEM TO |
| | INDICATE A BUS-DUCT FROM NORMAL MDS2 TO |
| | EDS, YET RISER SHOWS CONDUITS AND |
| | FEEDERS. PLEASE CORRELATE AND ALSO SEE |
| | FORTH COMING COMMENTS WITH RESPECT TO |
| | CONDUCTORS AND SIZES. |
| | |
| | 43) NOTE: PLEASE SEE DETAIL FOR FC ROOM, |
| | WHICH A 2' TABLE FOR PLAN/LAYOUT REVIEW, |
| | HOWEVER OVERVIEW OF ROOM DOES NOT SHOW |
| | THIS? |
| | |
| | |
| | 44) NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| | ALL SIGNAGE AND MAPPING TO BE LOCATED IN |
| | MAIN ELECTRICAL ROOM, FIRE COMMAND ROOM |
| | ETC. |
| | 230.2E,700.8 ETC. |
| | PLEASE KNOW, ALL PERMANENT SIGNAGE SHALL |
| | CONTAIN A MINIMUM OF 1 INCH LETTERING ON |
| | A CONTRASTING BACKGROUND. PLEASE KNOW, |
| | MAPPING SHOWING THE PATHS FOR ACCESS TO |
| | SYSTEMS WILL BE REQUIRED AT FC ROOM |
| | LOCATION. |
| | |
| | 45) NOTE: PLEASE PROVIDE ROOM/AREA |
| | DESIGNATIONS FOR INSIDE UNITS. |
| | 215.5 |
| | |
| | 46) NOTE: PLEASE SEE CIRCUITING FOR |
| | DINING ROOMS AND AREAS OF THE LIKE SHALL |
| | BE ON ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS. |
| | 210.52B1. |
| | UNABLE TO VERIFY. |
| | |
| | 47) NOTE: PLEASE SEE MINIMUM FACILITIES |
| | FOR CONDO UNITS FOR WASHER/LAUNDRY, |
| | DRYERS. |
| | PLEASE VERIFY , IF UNITS ARE GOING TO BE |
| | OWNED CONDOS? |
| | 220.16,220.18,210.11C1,210.52B |
| | |
| | 48) NOTE: PLEASE VERIFY PANELS IN UNITS |
| | AS THESE ARE SHOWN AS 225A, WITH |
| | 30CIRCUITS? PLEASE KNOW THIS IS NOT A |
| | COMMON SIZE. |
| | 215.5 SEE NEXT COMMENT. |
| | |
| | 49) NOTE: PLEASE CORRELATE ALL UNIT |
| | PANELS, OCP AND SIZES. |
| | PLEASE SEE RISER INDICATES PANELS AS |
| | 100A?S, HOWEVER MANY UNITS ARE 125A |
| | FEEDS/ OCP ON THESE 100A PANELS. PLEASE |
| | ALSO SEE PANELS ARE SHOWN AS 225A? |
| | |
| | 50) NOTE: PLEASE SEE PANEL WHICH ARE |
| | SHOWN WITH 150A OCP ON 100A PANELS. SEE |
| | GI, I, |
| | 215.5 |
| | |
| | 51) NOTE: PLEASE SEE RISER DOES NOT |
| | INDICATE PANEL "G1" , ONLY SHOWS "G"? |
| | PLEASE CORRELATE. |
| | PLEASE ALSO SEE THESE ARE ALL SHOWN AS |
| | 100A. |
| | 215.5 |
| | |
| | |
| | 52) NOTE: PLEASE SEE MANY UNITS WHICH |
| | SHOW THE CONTROL FOR SWITCHING THE |
| | RECEPTS. THIS IS OK, HOWEVER PLEASE SEE |
| | PLANS INDICATE SWITCHING OF THE ENTIRE |
| | DEVICE. PLEASE KNOW, THIS IS OK, HOWEVER |
| | AN ADDITIONAL RECEPT WILL BE REQUIRED TO |
| | MEET OUTLET SPACING PER 210.52, 210.70 |
| | THIS APPEARS TO BE A MISPRINT? PLEASE |
| | CORRELATE AND ADJUST. |
| | 215.5 |
| | |
| | 53) NOTE: PLEASE SEE WHAT APPEARS TO BE |
| | TWO DIFFERENT SCALES USED FOR UNIT |
| | PLANS. PLEASE SEE SOME SHOWN AS 3/8 INCH |
| | AND OTHERS AS 1/4 INCH. |
| | PLEASE SEE T-06, P-05. |
| | PLEASE SEE THESE SEEM TO BE THE SAME |
| | SIZE. |
| | 215.5 |
| | |
| | 54) NOTE: PLEASE VERIFY ALL AIC RATINGS |
| | ON PANELS AND BRANCH BREAKERS. PLEASE |
| | KNOW, IF PANELS MENTION 42K FOR RATINGS, |
| | THEN IT WILL BE ASSUMED THIS IS FOR BUS |
| | AND BRKR. |
| | 110.9,215.5 |
| | PLEASE CLARIFY. |
| | |
| | 55) NOTE: PLEASE VERIFY ALL RANGES/COOK |
| | TOPS IN UNITS. PLEASE SEE SOME UNITS ARE |
| | SHOWN AS 4-BURNER AND SOME AS WHAT |
| | APPEARS TO BE 2-BURNERS? IN EITHER CASE |
| | PLEASE VERIFY THE 2-20A BREAKER FEEDING |
| | THESE UNITS AND THE KW RATINGS AS SOME |
| | UNITS ARE LARGER, YET BOTH SHOW THE SAME |
| | LOAD AND OCP? |
| | 215.5 |
| | |
| | 56) NOTE: PLEASE SEE NOTES FOR KITCHEN |
| | GFI RECEPTS REFERENCE THE WRONG CODE. |
| | SHOULD BE 210.8A6. |
| | |
| | 57) NOTE: PLEASE SEE NOTEON DRAWING |
| | NOTES WHICH MENTIONS DINING ROOMS TO BE |
| | GFI PER 210.52B1? PLEASE KNOW, 210.52B1 |
| | DOES NOT MENTIONS GFI PROTECTION |
| | REQUIRED FOR DINING ROOM RECEPTS. PLEASE |
| | SEE DINING ROOM RECEPTS SHALL BE ON ONE |
| | OR MORE OF THE 20A SMALL APPLIANCE |
| | CIRCUITS. |
| | |
| | 58) NOTE: PLEASE VERIFY ALL MAINS , |
| | MDS1, MDS2, AND EDS2 AS CONTAINING A |
| | MANUAL MEANS OF DISCONNECT LOCATE DON |
| | THE OUTSIDE OF THE EQUIPMENT PER |
| | 230.76,230.79. |
| | THESE ARE ALL NOTED AS BEING SHUNT TRIP, |
| | HOWEVER THESE ARE ALSO REQUIRED TO HAVE |
| | DISC?S PER ABOVE. |
| | |
| | 59) NOTE: PLEASE VERIFY GROUND FAULT |
| | PROTECTION SHOWN FOR MDS1? |
| | PLEASE SEE 240.13, 230.95 ETC WHERE THE |
| | GFP IS REQUIRED AND NOTE REQUIRED. GFP |
| | IS NOT REQUIRED ON THIS MAIN, HOWEVER |
| | MAY BE INSTALLED. |
| | |
| | 60) NOTE:PLEASE SEE 230.13, 230.95, |
| | 700.7D, 700.26, NFPA-110 6.2.15*, WITH |
| | RESPECT TO GROUND FAULT PROTECTION ON |
| | EMERGENCY SIDE OF ED SYSTEM. PLEASE SEE |
| | SENSING OF GROUND FAULT AND ISOLATION OF |
| | NEUTRAL IS DESIRED, HOWEVER GFP ON THE |
| | EM SIDE O THE DISTRIBUTION SYSTEM IS NOT |
| | DESIRED. PLEASE SEE CODE COMMENTARY FOR |
| | FURTHER EXPLANATION. |
| | |
| | 61) NOTE: PLEASE SEE RISER NOTES AS GFP |
| | IS BEING NOTED FOR ALL SYSTEMS AND ATS'S |
| | ON THE EM DISTRIBUTION SIDE. PLEASE SEE |
| | THE NOTE IS REFERENCING THE NEC ARTICLE |
| | 517?? |
| | PLEASE SEE 517 IS FOR HEALTH CARE |
| | FACILITIES AND DOES NOT APPLY FOR THIS |
| | BUILDING OR SCOPE. |
| | PLEASE VERIFY THE ABOVE AND ADJUST RISER |
| | AS NEEDED. |
| | |
| | 62) NOTE: PLEASE PROVIDE GROUNDING |
| | ELECTRODE SYSTEM DETAIL FOR THE |
| | SEPARATELY DERIVED GENERATOR AS SHOWN. |
| | 250.30, 250.50 |
| | |
| | 63) NOTE: PLEASEPROVIDE ATTACHMENT |
| | LOCATION FOR ALL TRANSFORMERS PER 250.30 |
| | IT IS NOTED THAT A GROUND RISER WAS |
| | SHOWN. |
| | |
| | 64) NOTE: PLEASE SEE 250.104 WHICH |
| | REQUIRE ALL OTHER METAL PIPING SYSTEMS |
| | TO BE BONDED. |
| | ( FIRE SPRINKLER ETC) |
| | |
| | 65) NOTE: PLEASE SEE7.9.3.1 |
| | GALVANIZED FUEL LINES SHALL NOT BE USED. |
| | NFPA-110 7.9 |
| | |
| | 66) NOTE: PLEASE SEE 450.3, MAX OCP FOR |
| | THE LINE SIDE OF TRANSFORMERS SHALL BE |
| | 125%. IT IS PERMITTED TO GO THE NEXT |
| | SIZE UP WHEN THE AMPERAGE DOES NOT |
| | CORRELATE TO THE OCP DEVICE. PLEASE SEE |
| | EEL22 WHICH EXCEEDS THIS 125% |
| | |
| | 67) NOTE: PLEASE SEE EE22 IS SHOWN AS |
| | 400A ON RISER, YET SHOWN AS 225A ON |
| | PANEL SCHEDULE. |
| | 215.5 PLEASE CORRELATE. |
| | |
| | 68) NOTE: PLEASE SEE EE2 WHICH IS SHOWN |
| | AS 200A ON RISER AND SHOWN AS 225A ON |
| | PANEL SCHEDULE. PLEASE CORRELATE. 215.5 |
| | |
| | 69) NOTE: PLEASE SEE RISER SHOWS EH3 AS |
| | 400A ON RISER AND 600A ON SCHEDULE. |
| | PLEASE CORRELATE.215.5 |
| | |
| | 70) NOTE: PLEASE SEE EL3, 200A ON RISER |
| | AND 225A ON SCHEDULE. |
| | 215.5 |
| | |
| | 71) NOTE: PLEASE BE SURE TO GO THROUGH |
| | ALL FEEDS TO TRANSFORMERS. PLEASE SEE |
| | EH3, SHOWS A NEUTRAL CONDUCTOR WITH |
| | FEEDERS TO TRANSFORMER? PLEASE KNOW, |
| | THESE ARE SEPARATELY DERIVED SYSTEMS |
| | WHICH CREATE A NEW SYSTEM NEUTRAL. |
| | PLEASE SEE 250.6, 250.24B, 250.30 ETC. |
| | 215.5 |
| | |
| | 72) NOTE: PLEASE SEE ATS-1 ON RISER IS |
| | NOTED AS 260A'S? |
| | PLEASE CORRELATE AS THIS IS FED FROM A |
| | 200A DEVICE AND 260A'S IS NOT A COMMON |
| | SIZE. |
| | 215.5 |
| | |
| | 73) NOTE: PLEASE SEE 240.3 AS DEVICES |
| | RATED OVER 800A'S SHALL CONTAIN |
| | CONDUCTORS RATED AT OR ABOVE THE OCP |
| | PROVIDED. |
| | PLEASE SEE FEEDER NOTED TO ATS-2 FROM |
| | EDS2. |
| | PLEASE ALSO SEE FEEDER FROM MDS2 WHICH |
| | SHOWS THE SAME FEEDER #7. |
| | PLEASE SEE MDS2 AS THIS FEEDER ON |
| | SCHEDULE DOES NOT CORRELATE WITH THIS. |
| | 215.5 |
| | |
| | 74) NOTE: PLEASE SEE RISER SHOWS PANEL |
| | PC-2 AS 225A WITH 400A OCP FEEDING THIS |
| | PANEL. |
| | 240, 215.5 ETC |
| | |
| | 75) NOTE: PLEASE SEE PANEL PM-2 SHOWS |
| | 400A OCP FEEDING A PANEL RATED AT |
| | 225A'S. |
| | 240.4,408,215.5. |
| | |
| | 76) NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| | PM-2, PLEASE SEE AMPS IS SHOWN AS BLANK. |
| | 215.5 |
| | PLEASE ALSO SEE THIS SAME PANEL MENTIONS |
| | FED FROM MSD2, WHEN IT SHOULD BE MDS2. |
| | (MISPRINT?) |
| | |
| | 77) NOTE: PLEASE SEE PANEL PC-2 SHOWS |
| | AMP'S AS BLANK. |
| | 215.5 |
| | PLEASE ALSO SEE THIS SAME PANEL DETAILS |
| | BEING FED FROM MSD2, WHEN IT SHOULD READ |
| | MDS2. (MISPRINT?) |
| | |
| | 78) NOTE: PLEASE ADJUST FEEDERS TO BOTH |
| | PC-2 AND PM-2 DEPENDING ON SIZE AND |
| | RATING OF PANELS. PLEASE SEE PREVIOUS |
| | COMMENTS WITH RESPECT TO OCP FEEDING |
| | THESE PANELS. |
| | 215.5, 310.16, 240.4 |
| | |
| | 79) NOTE:PLEASE SEE KL2 WHICH MENTIONS |
| | FED FROM PM22? THIS DOES NOT CORRELATE |
| | WITH RISER? |
| | |
| | 80) NOTE: PLEASE SEE 2002 NEC 210.8B3 |
| | FOR ALL RECEPTS LOCATED IN KITCHENS |
| | 15/20A 125VTO BE GFIPROTECTED. |
| | PLEASE KNOW, THIS IS REQUIRED WHETHER OR |
| | NOT THESE ARE COUNTER SPACE RECEPTACLES. |
| | |
| | 81) NOTE: PLEASE SEE PL-2 WHICH SHOWS |
| | BEING FED FROM MSD2, INSTEAD OF MDS2. |
| | PLEASE ALSO SEE THE AMPERAGE IS SHOWN |
| | BLANK? |
| | PLEASE CORRELATE AND COMPLETE. 215.5 |
| | |
| | 82) NOTE: PLEASE SEE MISPRINT? FOR KP-2, |
| | MDS2, MSD2. |
| | 215.5 |
| | |
| | 83) NOTE: PLEASE SEE RISER SHOWS HP-1, |
| | AND PANEL HP-2 AS 100A'S AND PANEL |
| | SCHEDULE SHOWS THIS AS 225A'S.? |
| | PLEASE CORRELATE. 215.5 |
| | |
| | 84) NOTE: PLEASE ALSO SEE NUMEROUS |
| | PANELS WHICH ARE SHOWN AS 100A'S, YET |
| | THESE ARE SHOWN AS 42 CIRCUIT PANELS. |
| | THE # OF CIRCUITS AVAILABLE FOR THESE |
| | 100A?S PANEL SHOULD BE VERIFIED. |
| | 215.5 |
| | |
| | 85) NOTE: PLEASE INDICATE ALL CONDUCTORS |
| | ON THE SECONDARY SIDE OF TRANSFORMERS. |
| | PLEASE PROVIDE A TRANSFORMER SCHEDULE |
| | SHOWING. |
| | 215.5, 310.16, 240.4 ETC. |
| | THESE CAN NOT BE VERIFIED AT THIS TIME. |
| | |
| | 86) NOTE: PLEASE CLARIFY THE TWO |
| | DIFFERENT PANEL/UNIT CALCULATIONS ON |
| | UNIT LAYOUT SHEETS? |
| | PLEASE ONLY SHOW ONE AND CORRELATE WITH |
| | NOTES BELOW. |
| | 215.5 |
| | |
| | 87) NOTE: PLEASE SEE UNIT C WHICH SHOWS |
| | 87A'S AND SHOWN AS 86 ON LOAD SUMMARY? |
| | 215.5 |
| | |
| | 88) NOTE: PLEASE SEE ALL DP PANELS' |
| | SCHEDULES WHICH FEED HOUSE PANELS. |
| | PLEASE SEE HOUSE LOADS ARE SHOWN TAKING |
| | THE DE-RATINGFOR THE UNITS UNDER |
| | 220.32. PLEASE KNOW THE HOUSE PANEL |
| | LOADS CAN NOT BE DERATED WITH THESE |
| | DWELLING UNITS. |
| | 215.5 |
| | |
| | 89) NOTE: PLEASE SHOW ALL CONTINUOUS |
| | LOADS AND LARGEST MOTOR LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | PLEASE ADJUST ALL LOADS. |
| | |
| | 90) NOTE:PLEASE SEE PANEL G1 MISSING |
| | FROM RISER. PLEASE ALSO SEE PREVIOUS |
| | COMMENTS ABOVE WITH RESPECT TO |
| | CORRELATION OF OCP AND PANEL SIZES. |
| | 215.5 |
| | |
| | 91) NOTE: PLEASE SEE FIRE ALARM RISER |
| | WHICH INDICATES 120V POWER SUPPLY TO NAC |
| | PANELS, YET THESE ARE CIRCUITED ON THE |
| | 277/480V PANELS? |
| | |
| | 92) NOTE: PLEASE SEE NAC PANELS SHOWN ON |
| | RISER; HOWEVER THESE COULD NOT BE |
| | LOCATED ON PANEL SCHEDULE(S)? |
| | 215.5 |
| | |
| | 93) NOTE: PLEASE SEE KEYNOTE WHICH |
| | MENTIONS KITCHEN/ REST, BUT ONE COULD |
| | NOT BE LOCATED? |
| | |
| | |
| | 94) NOTE: PLEASE PROVIDE INFORMATION FOR |
| | LOADS, PANELS AND ELECTRICAL PROVISIONS |
| | BEING ALLOTTED FOR "FUTURE" TENANT |
| | SPACES. |
| | PLEASE SUBMIT LOAD FOR SQ FT ETC. |
| | 215.5 |
| | |
| | 95) NOTE:PLEASE SEE RETAIL COMMON |
| | "SHELL AREAS"CONTAIN MINIMUM LIGHTING |
| | AS REQUIRED AND PERFIRE MARSHAL'S |
| | OFFICE,LS 101 7.8, 7.9 HOWEVER PLEASE |
| | SEE THESE AREAS ARE ALL BEING SHOWN |
| | CIRCUITED TO PANELSWHICH UNDER THE |
| | BASE BUILDING. PLEASE PROVIDE NOTES ON |
| | PLANS, AS ALL OF THIS INTERIOR |
| | CIRCUITING WILL BE REQUIRED TO BE |
| | REMOVED AND RE-CIRCUITED TO THE PANELS |
| | AND SERVICE THESE TENANT SPACES ONCE |
| | PERMITTED. |
| | CROSSING OVER OF SERVICES, COMMON AREA |
| | BRANCH CIRCUITS IS NOT PERMITTED. |
| | 230.70, 225.25 ETC |
| | |
| | 96) NOTE: PLEASE SEE 700.12E WHICH |
| | REQUIRES ALL EM/EXT LTS TO BE CIRCUITED |
| | TO THE LOCAL BRANCH CIRCUIT FEEDING ANY |
| | ONE AREA. |
| | PLEASE SEE THIS IS NOTED ON PLANS, |
| | HOWEVER THERE ARE A COUPLE OF AREAS |
| | WHICH DO NOT LEND TO THIS CIRCUITING. |
| | 215.5 |
| | |
| | 97) NOTE: PLEASE KNOW, MANY OF THE ABOVE |
| | ITEMS ARE REDLINED ON ONE SET OF THE |
| | MEP'S FOR MANY OF THE SD'S, RECEPTS, |
| | LTS ETC AND LOCATIONS OF COMMENTS. |
| | PLEASE KNOW, THIS IS IN NO WAY ALL |
| | LOCATIONS WHICH MAY BE NEEDED. PLEASE GO |
| | OVER PLANS FOR ALL ITEMS. |
| | |
| | 98) NOTE: PLEASE KNOW A DETAILED |
| | RESPONSE LETTER ON HOW ALL COMMENTS WERE |
| | ADDRESSED AND CLARIFICATIONS NEEDED. |
| | THIS WILL HELP IN EXPEDITING THE REVIEW |
| | PROCESS. |
| | |
| | 99) NOTE: PLEASE SEE ALL COMMENTS FROM |
| | OTHER REVIEWS WHICH MAY AFFECT |
| | ELECTRICAL PLANS AND DESIGN. |
| | |
| | 100) NOTE:ONCE ALL REVIEWS ARE |
| | COMPLETE AND BEFORE RESUBMITTING PLANS: |
| | "ALL OLD/VOIDED SHEETS SHALL BE REMOVED |
| | AND ONLY THE NEW REVISED SHEETS SHOULD |
| | BE INSERTED INTO THREE COMPLETE SETS FOR |
| | REVIEW AND STAMPING". |
| | ONE SET OF ALL OLD/VOIDED SHEETS WHICH |
| | ARE REMOVED SHOULD BE SUBMITTED FOR |
| | REFERENCE ALONG WITH THE NEW SETS. ALL |
| | VOIDED SHEETS MUST BE REMOVED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-04-07 00:00:00 | PLANS WILL GO INTO FAILED STATUS. |
| | |
| | ** REVIEW TO CONTINUE ON 4/10. |
| | |
| | COMMENTS TO FOLLOW. |
| 2006-04-05 00:00:00 | REVIEW COMMENCED |
| 2006-03-29 00:00:00 | ONE ROLL OF PLANS IN ELECTRIC FOR |
| | REVIEW. |