| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | DENIED |
| | |
| | 1) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE |
| | MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHEN APPROVED |
| | BY THE BUILDING OFFICAL. CONSTRUCTION |
| | DOUCMENTS SHALL BE OF SUFFICENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT ITWILL CONFORM TOTHE |
| | PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS |
| | AS DETERMINED BY THE BUILDING OFFICAL ( |
| | SEE ALSO SECTION 106.3.5) |
| | 2) SHT LS0-0 REQUIRED MINIMUM FACILITIES |
| | SHOW THE LOCATION OF THE REQUIRED D/F |
| | AND S/S, REFERENCED ON CODE SUMMARY. |
| | 3) SHT A1-1.0 ROOM #108,109 DARK ROOM. |
| | SEC 803.2 NEUTRALIZING DEVICE REQUIRED |
| | FOR CORROSIVE WASTE. |
| | CONTACT W P BEACHWATERPLANT LAB |
| | SUPERVISORINDUSTRIAL COORDINATOR, |
| | LYNN MASSON |
| | OFFICE 561-822-2271 |
| | E-MAIL [email protected] |
| | 4)SHT A1-1.0 SEC 415 GROUP H-5 |
| | OCCUPANCY. ROOM #110,111 JEWELRY MFG. |
| | STUDIO. PROVIDE IN DETAIL ALL |
| | INFORMATION REQUIRED FOR GROUP H-5 USE. |
| | 5) SHT A1-1.0 CONFERENCE RM SINK. |
| | 11-4.24 SINKS. |
| | 11-4.24.1 GENERAL. |
| | SINKS REQUIRED TO BE ACCESSIBLE BY |
| | SECTION 11-4.1 SHALL COMPLY WITH SECTION |
| | 11-4.24. |
| | 11-4.24.2 HEIGHT. |
| | SINKS SHALL BE MOUNTED WITH THE COUNTER |
| | OR RIM NO HIGHER THAN 34 INCHES (865 MM) |
| | ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE. |
| | KNEE CLEARANCE THAT IS AT LEAST 27 |
| | INCHES (685 MM) HIGH, 30 INCHES (760 MM) |
| | WIDE, AND 19 INCHES (485 MM) DEEP SHALL |
| | BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.4 DEPTH. |
| | EACH SINK SHALL BE A MAXIMUM OF 6? |
| | INCHES (165 MM) DEEP. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES |
| | BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE |
| | PROVIDED IN FRONT OF A SINK TO ALLOW |
| | FORWARD APPROACH. THE CLEAR FLOOR SPACE |
| | SHALL BE ON AN ACCESSIBLE ROUTE AND |
| | SHALL EXTEND A MAXIMUM OF 19 INCHES (485 |
| | MM) UNDERNEATH THE SINK (SEE FIGURE |
| | 11-32). |
| | 11-4.24.6 EXPOSED PIPES AND SURFACES. |
| | HOT WATER AND DRAIN PIPES EXPOSED UNDER |
| | SINKS SHALL BE INSULATED OR OTHERWISE |
| | CONFIGURED SO AS TO PROTECT AGAINST |
| | CONTACT. THERE SHALL BE NO SHARP OR |
| | ABRASIVE SURFACES UNDER SINKS. |
| | 11-4.24.7 FAUCETS. |
| | FAUCETS SHALL COMPLY WITH SECTION |
| | 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, |
| | TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED |
| | MECHANISMS ARE ACCEPTABLE DESIGNS. |
| | 6)SEC 106.3.5.1.3 (3,4.)COMMERICAL |
| | BUILDINGS: PLUMBING, SANITARY; WATER. |
| | ISOMETRIC REQUIRED. |
| | 7) SEC 106.3.5.2 GAS: ISOMETRIC |
| | REQUIRED. |
| | 8)PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT PLUMBING |
| | PLANS. |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |
| | |
| | |