| Plan Review Notes For Permit 06010290 |
| Permit Number |
06010290 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-15 00:00:00 | ******DENIED****** | | | | | | 1) NFPA 101, AND NFPA-1 2003 EDITION | | | SHALL BE REFERENCED. PLEASE MAKE | | | CORRECTION ON SHT T-1. | | | | | | 2) RAMPS AND STAIRS SHALL HAVE HANDRAILS | | | ON BOTH SIDES. | | | | | | 3) MONTGOMERY HALL OCCUPANT LOAD IS | | | INCORRECT. CALCULATION WAS BASED ON 5 | | | SQ'/PERSON, HOWEVER 15 SQ'/PERSON SHOULD | | | BE USED. | | | | | | 4) PLEASE INDICATE THE INTERIOR FINISH | | | CLASSIFICATION OF WALLS AND CEILINGS, | | | CLASS A,B,OR C. | | | | | | 5) SEPARATE SHOP DRAWING AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 6) EXIT DOORS SERVING OCCUPANT LOADS | | | GREATER THAN 100 SHALL HAVE PANIC | | | HARDWARE. PLEASE SHOW ON DOOR SCHEDULE. | | | | | | | | | 7) A CURRENT OCCUPANT LOAD SIGN MAY BE | | | OBTAINED FROM THE BUREAU OF FIRE | | | PREVENTION IF DIFFERENT FROM LAST | | | CACULATION. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (%^1) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|