Plan Review Notes
Plan Review Notes For Permit 06010290
Permit Number 06010290
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-02-15 00:00:00******DENIED******
  
 1) NFPA 101, AND NFPA-1 2003 EDITION
 SHALL BE REFERENCED. PLEASE MAKE
 CORRECTION ON SHT T-1.
  
 2) RAMPS AND STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 3) MONTGOMERY HALL OCCUPANT LOAD IS
 INCORRECT. CALCULATION WAS BASED ON 5
 SQ'/PERSON, HOWEVER 15 SQ'/PERSON SHOULD
 BE USED.
  
 4) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILINGS,
 CLASS A,B,OR C.
  
 5) SEPARATE SHOP DRAWING AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 6) EXIT DOORS SERVING OCCUPANT LOADS
 GREATER THAN 100 SHALL HAVE PANIC
 HARDWARE. PLEASE SHOW ON DOOR SCHEDULE.
  
  
 7) A CURRENT OCCUPANT LOAD SIGN MAY BE
 OBTAINED FROM THE BUREAU OF FIRE
 PREVENTION IF DIFFERENT FROM LAST
 CACULATION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (%^1) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  