| 2006-02-10 00:00:00 | IN ELEC FOR REVIEW | | | ******** UNSAT ********** | | | | | | 1)NOTE: PLEASE INDICATE ALL CIRCUITING | | | ON PLANS AND CORRELATE A PANEL SCHEDULE | | | OR PANEL SCHEDULE(S) TO BE SUBMITTED. | | | NEW OR EXISTING PANELS BEING ADDED FOR | | | WORK/ CIRCUITS? | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE MANY NEW 30A RECEPTS | | | ARE INDICATED. PLEASE ALSO SEE PLANS | | | INDICATE 60A RECEPTS ALSO WITH OUT ANY | | | INFORMATIONFOR LOADS DEVICES ETC. | | | PLEASE SUBMIT LOAD CALCUALTIONS FOR ALL | | | EXISITNG AND NEW TO BE ADDED. PLEASE | | | ALSO SPECIFY USE OF THE NEW DEVICES AND | | | LOADS. | | | 215.5,220 | | | | | | 3)NOTE: PLEASE SEE SHEET T-1 WHICH | | | INDICATES A 2004 NFPA-101. PLEASE KNOW, | | | AS OF JAN 1ST, 2005 WE ARE CURRENTLY | | | UNDER THE 2003 NFPA-101. | | | | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|