| Plan Review Notes For Permit 06010282 |
| Permit Number |
06010282 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-02-28 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: | | | 1- PRODUCT APPROVAL FOR POLYGLASS USA | | | MODIFIED BITUMEN ROOF SYSTEM IS LIMITED | | | BY GENERAL LIMITATION #7, WHICH REQUIRES | | | REQUIRES ENHANCED UPLIFT CALCULATIONS | | | FOR ROOF SYSTEM AT PERIMETER AND CORNER | | | AREAS TO BE PREPARED, SIGNED AND SEALED | | | BY A PROFESSIONAL AS LISTED IN | | | LIMITATION #7. | | | SUCH CALCULATIONS NEED TO BE DONE IN | | | COMPLIANCE WITH ROOFING APPLICATION | | | STANDARD RAS 117. CALCULATIONS SUBMITTED | | | BY THE PROFESSIONAL ENGINEER RICHARD | | | BOYETTE DON'T ADDRESS THE STANDARD CITED | | | ON LIMITATION #7. NEED CALCULATIONS FOR | | | THE ENHANCING OF THE FLAT ROOF SYSTEM TO | | | BE INSTALLED, NOT THE ROOF SHEATHING. | | | ENGINEER TO READ LIMITATION #7 AND | | | PROVIDE REQUESTED CALCULATIONS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. | | | |
|