2006-01-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-REPLACING STEEL DECKING IS
 CONSIDERED STRUCTURAL WORK. ROOFING
 CONTRACTOR IS NOT ALLOWED TO PERFORM
 STRUCTURAL WORK. NEED CONTRACTOR THAT
 CAN PERFORM THIS STRUCTURAL WORK PRIOR
 TO INSTALL ROOFING MATERIAL. SEE DBPR
 FOR SCOPE OF WORK ALLOWED FOR ROOFING
 CONTRACTORS.
  
 2- FLORIDA PRODUCT APPROVAL #FL 5186.2
 IS FOR STEEL DECK. ACCORDING TO
 INFORMATION SUBMITTED THE DECK TYPE IS
 LIGHT WEIGHT CONCRETE. THEREFORE,
 PRODUCT APPROVAL AND ACTUAL INSTALLATION
 DON'T MATCH. REVISE AS REQUIRED.
  
 3- A) FORENSIC ENGINEERING CALCULATIONS
 ARE INCOMPLETE. THEY DON'T SPECIFY
 PRODUCT APPROVAL NUMBER AND SYSTEM
 DESIGN PRESSURES. WHAT REFERENCE IS THE
 ENGINEER USING TO INCREASE THE UPLIFT
 CAPACITY OF THE SYSTEM IF INFORMATION OF
 SYSTEM TO BE UPGRADED IS NOT KNOWN. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2001.
  
 B) ENGINEER TO VERIFY THAT PROPOSED
 ASSEMBLY IS THE SAME ASSEMBLY THE
 PRODUCT APPROVAL IS DESIGNED FOR. EG:
 THE DECK IS LIGHT WEIGHT CONCRETE NOT
 STEEL. AND PROVIDE CALCULATIONS BASED ON
 THAT CRITERIA. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) ENGINEER TO SPECIFY HOW LONG ARE THE
 FASTENERS. REMEMBER LIGHT WEIGHT
 CONCRETE DECK.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712