| 2006-01-31 00:00:00 | |
| | NO COMMENTS FROM THE PREVIOUS REVIEW |
| | WERE ADDRESSED. |
| | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PROVIDE THE AIC RATING FOR THE |
| | SERVICE EQUIPMENT PER 110.9. |
| | |
| | 2} SUBMIT A PANEL SCHEDULE SO THAT |
| | BRANCH CIRCUIT COMPLIANCE CAN BE |
| | REVIEWED. |
| | |
| | 3} THE REFERENCE IN THE ELECTRICAL NOTES |
| | TO THE 2001 NEC ARE INCORRECT, WE ARE |
| | CURRENTLY UNDER THE 2002 EDITION. |
| | |
| | 4} THE 3 SMALL APPLIANCE CIRCUITS IN THE |
| | LOAD CALCULATION MUST BE 1500 VA EACH |
| | PER 220.16(A). |
| | |
| | 5} A RECEPTACLE MUST BE ADDED IN BEDROOM |
| | #3 TO COMPLY WITH 210.52(A)(1). |
| | |
| | 6} A SMOKE DETECTOR IS REQUIRED OUTSIDE |
| | BEDROOM #3 PER 313.1 FBC(RES). BECAUSE |
| | THIS WOULD PLACE IT IN THE KITCHEN SEE |
| | NFPA-72 ARTICLE 11.8.3.5(4) FOR |
| | REQUIREMENTS. |
| | |
| | 7} LOCATE A RECEPTACLE IN BEDROOM #1 TO |
| | COMPLY WITH 210.52(A)(2) AT ENTRANCE. |
| | SEE REVIEWED SET OF PLANS. |
| | |
| | 8} A RECEPTACLE MUST BE ADDED IN THE |
| | DINING ROOM PER 210.52(A)(1), ALSO SEE |
| | 210.52(B)(1). |
| | |
| | 9} THE LOAD CALC INDICATES TWO A/C |
| | SYSTEMS, THERE IS ONLY ONE SHOWN ON THE |
| | DRAWINGS. PLEASE CORRELATE. |
| | |
| | |
| | ATTACHED IS THE REQUIRED VIOLATION |
| | NOTICE ADDRESSED TO THE DESIGN |
| | PROFESSIONAL PER 553.80(2)(B)FLORIDA |
| | STATUTES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |