| 2006-01-20 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED |
| | ITEMS APPLY |
| | |
| | _XX_1.A NOTICE OF COMMENCEMENT MUST |
| | BE FILED WITH THE CLERK OF COURTS BEFORE |
| | A PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | ____2.PROVIDE BUILDING HEIGHT. |
| | DESIGN PRESSURES FOR BUILDINGS OVER |
| | 60FEET ARE REQUIRED TO BE DESIGNED USING |
| | ASCE7, FBC1609.1.1. DOCUMENTS PREPARED |
| | BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| | RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| | FAC61G15-23.002. |
| | |
| | ____3.PROVIDE A COPY OF THE CONDO |
| | ASSOCIATION APPROVAL. |
| | |
| | _XX_4.COMPLETE THE ATTACHED |
| | INSTALLATION SCHEDULE OR PROVIDE |
| | REQUIRED INFORMATION IN A SIMILAR |
| | FORMAT.**INSTALLATION SCHEDULE WAS |
| | COMPLETED BUT THE WALL PRESSURES ARE NOT |
| | CORRECT.SEE ATTACHED FBC TABLE |
| | 1609.6B.THE COLUMN FOR SHUTTER SPAN |
| | HAS THE SF TOTAL.ADDRESS. |
| | |
| | ____5.FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | _XX_6.ON THE PRODUCT APPROVAL, MARK |
| | WHICH DETAILS APPLY TO THIS JOB. |
| | **DETAILS WERE MARKED; ON SOME SHEETS |
| | ALMOST ALL DETAILS WERE MARKED.THE |
| | SCHEDULE DECLARES THE STRUCTURE AS |
| | MASONRY/CONCRETE, BUT WOOD ANCHORING WAS |
| | HIGHLIGHTED.ON THE ANCHOR CHARTS, |
| | CLEARLY INDICATE WHICH ANCHORS YOU ARE |
| | USING ALONG WITH SPACING, TO CORRELATE |
| | WITH THE INSTALLATION SCHEDULE. |
| | |
| | ____7.SHOW THE EMERGENCY MEANS OF |
| | ESCAPE, FBC R310 |
| | |