| Plan Review Notes For Permit 06010196 |
| Permit Number |
06010196 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-31 00:00:00 | *** DENIED *** | | | 1) PLEASE SHOW BATHROOM EXHAUST FAN ON | | | MECHANICAL PLAN. | | | | | | 2) NEED TO SHOW LOCATION OF CONDENSER | | | UNIT ON MECHANICAL PLAN. | | | | | | 3) PLEASE SHOW CONDENSATE DRAIN LINE ON | | | MECHANICAL PLAN. | | | | | | 4) 10X10 RETURN AIR GRILL IS TO SMALL | | | FOR A 1 1/2 TON UNIT. | | | | | | 5) RETURN AIR DUCT NEEDS TO BE AS LARGE | | | OR LARGER THAN THAN THE SUPPLY AIR DUCT. | | | | | | 6) PLEASE SHOW HEATER SIZE (KW) ON | | | MECHANICAL PLAN. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|