2006-01-31 00:00:00*** DENIED ***
 1) PLEASE SHOW BATHROOM EXHAUST FAN ON
 MECHANICAL PLAN.
  
 2) NEED TO SHOW LOCATION OF CONDENSER
 UNIT ON MECHANICAL PLAN.
  
 3) PLEASE SHOW CONDENSATE DRAIN LINE ON
 MECHANICAL PLAN.
  
 4) 10X10 RETURN AIR GRILL IS TO SMALL
 FOR A 1 1/2 TON UNIT.
  
 5) RETURN AIR DUCT NEEDS TO BE AS LARGE
 OR LARGER THAN THAN THE SUPPLY AIR DUCT.
  
 6) PLEASE SHOW HEATER SIZE (KW) ON
 MECHANICAL PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.