Plan Review Notes
Plan Review Notes For Permit 06010196
Permit Number 06010196
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-31 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A RISER DIAGRAM FOR THE
 PROPOSED SERVICE INDICATED ON THE PLAN.
 INCLUDE THE PANEL FOR THE CABANA AND
 COMPLIANCE WITH 225.31 AND 250.32.
  
 2} PROVIDE A PANEL SCHEDULES FOR THE NEW
 EQUIPMENT WHICH INCLUDE THE PANEL
 SPECIFICATIONS FOR BRANCH CIRCUIT
 CAPACITY, VOLT AND AMPERAGE RATINGS.
  
 3} INDICATE THE LOCATION OF THE A/C
 CONDENSING UNIT AN DISCONNECT.
  
 4} PLEASE INDICATE GFI RECEPTACLES PER
 210.8(A)(7) IN THE WET BAR AREA.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  