| 2006-01-31 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT A RISER DIAGRAM FOR THE | | | PROPOSED SERVICE INDICATED ON THE PLAN. | | | INCLUDE THE PANEL FOR THE CABANA AND | | | COMPLIANCE WITH 225.31 AND 250.32. | | | | | | 2} PROVIDE A PANEL SCHEDULES FOR THE NEW | | | EQUIPMENT WHICH INCLUDE THE PANEL | | | SPECIFICATIONS FOR BRANCH CIRCUIT | | | CAPACITY, VOLT AND AMPERAGE RATINGS. | | | | | | 3} INDICATE THE LOCATION OF THE A/C | | | CONDENSING UNIT AN DISCONNECT. | | | | | | 4} PLEASE INDICATE GFI RECEPTACLES PER | | | 210.8(A)(7) IN THE WET BAR AREA. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|