| 2006-03-30 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: |
| | |
| | 1- THIS IS THE THIRD TIME REQUESTING |
| | PEDESTRIAN WALKWAYACCESSIBILITY |
| | INFORMATION TO REVIEW COMPLIANCE WITH |
| | CHAPTER 11 FBC 2004. |
| | |
| | FIRST TWO TIMES THIS ITEM WAS NOT |
| | ADDRESSED AT ALL. THIS TIME THE ONLY |
| | INFORMATION SUBMITTED WAS NOTE #19 |
| | SAYING "BRIDGE SHALL BE INSTALLED TO |
| | MEET ADA ACCESSIBILITY REQUIREMENTS, |
| | RISE SHALL NOT EXCEED 5%. GUIDERAILS |
| | SHALL BE INSTALLED TO BOCA STANDARDS". |
| | THIS IS NOT ENOUGH INFORMATION FOR |
| | REVIEW AND SPECIFIED REFERENCES DON'T |
| | APPLY TO FLORIDA. |
| | (ENGINEER TO READ ATTACHED COPY OF |
| | FLORIDA STATUTE 553.80(2)(B) REGARDING |
| | DESIGN PROFESSI0NAL DOCUMENTS AND |
| | MULTIPLE REVIEWS) |
| | |
| | 2- DESIGNER OF RECORD NEED TO REVIEW |
| | CHAPTER 11 OF FLORIDA BUILDING CODE 2004 |
| | AND PROVIDE THE SPECIFIC INFORMATION |
| | THAT APPLIES TO THE PEDESTRIAN WALKWAY. |
| | |
| | 3- DRAWING # 203145-00 THAT HAS |
| | ADDITIONAL NOTE #19 IS PART OF THE |
| | CONSTRUCTION DOCUMENTS AND IS MISSING |
| | THE ENGINEER'S TITLE BLOCK, SEAL AND |
| | SIGNATURE. |
| | |
| | 4- FROM PREVIOUS CHECKLISTS ENGINEER WAS |
| | ASKED TO SUBMIT ALL DOCUMENTS WITH HIS |
| | ORIGINAL SEAL, SIGNATURE AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTE AND FLORIDA |
| | ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| | LAST PACKAGE SUBMITTED ADDRESSING THE |
| | FLORIDA PRODUCT APPROVALS REVIEW DOESN'T |
| | HAVE ORIGINAL SEAL AND SIGNATURE. |
| | |
| | 5- ENGINEER USES THE UZMAN ENGINEERING |
| | NAME ON WIND LOAD CALCULATIONS. SEE |
| | SHEET NUMBER 203145-01 OF LARGE SET OF |
| | DRAWINGS 24"X36" SHEETS. THAT'S WHY |
| | CERTIFICATE OF AUTHORIZATION WAS |
| | REQUESTED ON PREVIOUS CHECKLISTS. |
| | |
| | 6- THERE ARE TOO MANY SETS OF PLANS |
| | SUBMITTED. PLEASE SUBMIT ONLY TWO MOST |
| | RECENT SETS WITH ALL REQ'D INFORMATION |
| | (REVISIONS, TITLE BLOCK AND ORIGINAL |
| | SEAL AND SIGNATURE). |
| | PROVIDE LARGE SETS (24"X36" SHEETS) OR |
| | SMALL SETS (8 1/2"X11" SHEETS) NOT BOTH |
| | TO AVOID CONFUSIONS. THERE IS SOME |
| | INFORMATION THAT IS IN ONE SET BUT IS |
| | NOT IN THE OTHER. CHECK IT OUT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | ***NOTE: |
| | THIS PROJECT WAS BROUGHT TO THE |
| | ATTENTION OF MY SUPERVISORS ROBERT BROWN |
| | (PLANS EXAMINER MANAGER) AND NEIL MELICK |
| | (BUILDING OFFICIAL) BECAUSE I WANT TO |
| | ISSUE THE PERMIT, BUT COMMENTS HAVE NOT |
| | BEEN PROPERLY ADDRESSED. |