| 2006-01-23 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- SHEET NUMBER 203145-01: |
| | A) NEED REFERENCE OF CURRENT CODE FBC |
| | 2004. |
| | B) MISSING WIND LOAD INFORMATION. SEE |
| | SEC. 1603.1.4 FBC 2004. |
| | |
| | 2- A) ENGINEER TO PROVIDE ORIGINAL SEAL |
| | AND SIGNATURE IN ALL SHEETS OF SUBMITTED |
| | DRAWINGS AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES AND 61G15-23.002 OF |
| | FLORIDA ADMINISTRATIVE CODE. SEE |
| | ATTACHED COPY. |
| | |
| | B) ENGINEER TO PROVIDE ALL HIS |
| | INFORMATION IN THE TITLE BLOCK AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTES |
| | AND 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE. SEE ATTACHED COPY. |
| | |
| | C) PROVIDE COMPANY'S FLORIDA |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS |
| | REQUIRED BY 61G15-23 OF FLORIDA |
| | ADMINISTRATIVE CODE. SEE ATTACHED COPY. |
| | |
| | 3- PERMIT APPLICATION SAYS "CONSTRUCTION |
| | OF A PEDESTRIAN WALKWAY OVER THE |
| | M-CANAL". PEDESTRIAN WALKWAYS NEED TO |
| | COMPLY WITH THE REQUIREMENTS OF CHAPTER |
| | 11 OF FBC 2004 (FLORIDA ACCESSIBILITY |
| | CODE). DRAWINGS TO SHOW HOW PEDESTRIAN |
| | WALKWAY COMPLIES WITH THE REQUIREMENTS |
| | OF THIS CHAPTER. OTHERWISE, PROVIDE |
| | INFORMATION THAT EXEMPTS PEDESTRIAN |
| | WALKWAY TO COMPLY WITH THIS CHAPTER. |
| | |
| | 4- ACCORDING TO CONFIDENTIALITY NOTE ON |
| | SHEET 203145-01 THESE CONSTRUCTION |
| | DOCUMENTS ARE FOR YBC TO BUILD THE |
| | BRIDGE. PROVIDE AUTHORIZATION FROM YBC |
| | TO MURRAY LOGAN CONSTRUCTION INC. TO USE |
| | DRAWINGS TO BUILD BRIDGE. |
| | |
| | 5- A) PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR SIMPSON CONNECTORS (H5-SS |
| | AND MSTA12-SS) SPECIFIED ON PLANS AS |
| | REQUIRED BY RULE 9B-72 OF DEPARTMENT OF |
| | COMMUNITY AFFAIRS. |
| | |
| | B) ENGINEER OF RECORD TO REVIEW AND |
| | APPROVED ABOVE PRODUCT APPROVALS PRIOR |
| | TO SUBMITTAL TO THIS OFFICE AS REQUIRED |
| | BY SEC. 106.3.3 OF CITY AMENDMENTS TO |
| | FBC 2001. |
| | |
| | 6- THERE SEEMS TO BE A TYPO ON |
| | SPECIFICATIONS FOR CONCRETE APPROACH PAD |
| | AT BOTH SIDES OF BRIDGE. IT SHOULD READ |
| | 6'-0" LONG BY 14'-0" WIDE CONCRETE PAD, |
| | NOT 6'-0" LONG BY 14" WIDE CONCRETE PAD. |
| | REVISE SHEETS 203145-03 AND 203145-08 |
| | ACCORDINGLY. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |