| Plan Review Notes For Permit 06010186 |
| Permit Number |
06010186 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-04 00:00:00 | | | | 1) SUBMIT A DETAIL UL ASSEMBLY DRAWING | | | FOR THE ONE HOUR RATED WALL. THE | | | INFORMATION SUBMITTED IS INADEQUATE. | | | | | | 2) ON SHEET #5 WHAT TYPE OF FIRE | | | BLOCKING MATERIALS WILL BE USED AT THE | | | FLOORS AND CEILINGS. STATE THIS | | | INFORMATION ON THE DRAWINGS. IN | | | REFERENCE TO THE STATEMENT "FIRE RATED | | | INSULATION AS PER CODES" EXPLAIN WHERE | | | AND HOW THE INSULATION WILL BE | | | INSTALLED. SAYING AS PER CODE IS NOT | | | SUFFICENT INFORMATION. SEE NOTES FROM | | | ELECTRIACAL REVIEWER. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | | | | |
|