Plan Review Notes
Plan Review Notes For Permit 06010172
Permit Number 06010172
Review Stop G
Sequence Number 1
Notes
Date Text
2006-01-18 00:00:00DENIED
  
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS. THE DRAWING SUBMITTED IS NOT
 AN ISOMETRIC AND HARD TO READ.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NEED SUBMITTAL ON 2# GAS REGULATERS,
 NOTE: POOL HEATER PASSED WITH POOL
 PERMIT.
 4. GAS PERMIT CAN'T BE ISSUED UNTIL
 GENERATOR PERMIT IS APPROVED BY ZONING.
 GENERATOR PLACEMENT APPROVAL BY ZONING
 MIGHT REQUIRE MORE GAS PIPE. CHECK WITH
 ELECTRICAL CONTRACTOR, OR OWNER ON THIS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  