| Plan Review Notes For Permit 06010172 |
| Permit Number |
06010172 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-18 00:00:00 | DENIED | | | | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS. THE DRAWING SUBMITTED IS NOT | | | AN ISOMETRIC AND HARD TO READ. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | NEED SUBMITTAL ON 2# GAS REGULATERS, | | | NOTE: POOL HEATER PASSED WITH POOL | | | PERMIT. | | | 4. GAS PERMIT CAN'T BE ISSUED UNTIL | | | GENERATOR PERMIT IS APPROVED BY ZONING. | | | GENERATOR PLACEMENT APPROVAL BY ZONING | | | MIGHT REQUIRE MORE GAS PIPE. CHECK WITH | | | ELECTRICAL CONTRACTOR, OR OWNER ON THIS. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 | | | |
|