| Notes |
| Date |
Text |
| 2006-07-24 00:00:00 | *** DENIED *** | | | 1) AHU #1 12" TRUNK LINE IS TO SMALL FOR | | | 907 CFM'S SEE MANUAL 'J' CALCULATIONS | | | MAX. VELOCITY 900 FPM, THEREFORE 14" | | | WOULD BE REQUIRED. AND THE 10" TRUNK | | | LINE WOULD NEED TO BE 12", PLESE | | | CORRECT. | | | | | | 2) A/C SYSTEM #3 IS LISTED AS A 3.5 TON | | | BUT IS A 2.5 TON PLEASE CORRECT. | | | | | | 3) SEE 4" DUCT TO MEDIA ROOM AND 8" DUCT | | | TO WALKIN CLOSET, PLEASE CORRECT. | | | | | | 4) IS AHU #1 GOING IN THE PANTRY OR IN | | | THE ALOSET WITH THE WATER HEATER, SEE | | | ELECTRICAL PLANS AND MECHANICAL PLANS, | | | PLEASE CORRECT. | | | | | | 5) SEE 7" DUCT TO HIS CLOSET, PLANS ALSO | | | SHOW (2)6X6 1W 30 CFM, PLEASE CORRECT. | | | | | | 6) AHU IN MASTER SUITE IS MARKED AS AHU | | | #2 BUT IS AHU #3, PLEASE CORRECT. | | | | | | 7) AHU OVER UTILITY ROOM IS MARKED AS | | | AHU #3, BUT IS AHU #2, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|